Connecting Communication and Power Wiring - continued

•  Keep communications cables away from line voltage wiring, lighting ballasts, and other devices emitting 

EMF energy. Maintain a minimum of two (2) inches between line voltage wires and communications or zone 

controller cables.

•  Field provide a minimum of 18-2 AWG, stranded and shielded, PVC or vinyl jacket communications wiring 

between the indoor units, heat recovery boxes (if applicable), and outdoor units.

•  The outdoor/indoor unit communications cable must be run between components in a daisy chain configu-

ration. Star or wye configurations are not allowed.

•  Connect the communications cables to the A/3(A) and B/4(B) terminals at indoor units and/or heat recov-

ery units. Maintain polarity throughout the communications bus. Be sure A/3(A) terminals are connected to 

A/3(A) terminals and B/4(B) terminals are connected to B/4(B) terminals.

•  Connect the shields of the communications cable segments together at each indoor unit. Insulate each 

shield connection to prevent electrical contact with the IDU. Ground the shield of the communications cable 

at one end only, at the master outdoor unit. 

Multi F and Single Zone Indoor Unit Wiring Configuration

Multi F and Single Zone IDUs have a single cable from the outdoor unit that supplies both power and commu-

nication. This field-supplied cable must be minimum 18-4 stranded and shielded. Be sure the power conduc-

tors are connected to the line power terminals of the IDU. Be sure the communication conductor is connect-

ed to the communication terminal of the IDU and ground is connected to ground.

Power Supply

(208/230V)

L(L1)   L(L2)     3

L(L1)

L(L2)

3 Communications

Ground

Typical Multi F and Single Zone IDU Power Wiring

and Communications Cable Terminals

Optional Wired Wall Controller Installation

Since the room temperature sensor is inside the remote controller, to maintain proper space temperature install the remote controller in a 

place away from direct sunlight, high humidity, and direct supply of hot or cold air.  Install the remote controller about 5 ft above the floor in 

an area with good air circulation and an average temperature.

  

 Do not install the remote controller where it can be affected by the following:

•  Drafts or dead spots behind doors and in corners

•  Hot or cold air from ducts

•  Radiant heat from sun or appliances

•  Concealed pipes and chimneys

•  Uncontrolled areas such as an outside wall behind the remote controller

1.  Pull communications cable between the zone controller handy box (if used) and 

the indoor unit. Use field supplied 22-3 twisted, stranded and unshielded cable 

or LG supplied cable. 

2.  Store a minimal amount of cable in the handy box. Any additional cable should be 

coiled and stored near the indoor unit control panel.

3.  If using LG cable and additional cable length is needed, order a thirty-three (33) 

foot LG Wired Remote Group Control Extension cable (Model No. PZCWRC1).

4.  If using LG supplied cable and the cable between the zone controller and the 

indoor unit is too long, do not cut the cable and shorten. Coil any spare commu-

nications cable, tie-wrap it, and leave it next to the indoor unit location.

5ft

no

no

no

yes

Remote Controller

TEMP

Remote Controller

TEMP

Rem

ote C

ont roller

TEM

P

 Typical Wired Remote Controller Installation

Lock nut

Conduit

1(L1) 2(L2)

3(A)

4(B)

Power Supply

High Voltage

(208/230V)

Communications

Typical Multi V 2-way Cassette IDU Power Wiring and Communications 

Cable Terminals

1(L1) 2(L2)

3(A)

4(B)

Power Supply

High Voltage

(208/230V)

Communications

Lock nut

Conduit

mounting

plate

Conduit

Typical Multi V 1-way Cassette IDU Power Wiring and Communications 

Cable Terminals

Summary of Contents for LCN188HV4

Page 1: ...em malfunction Do not install the unit in a noise sensitive area Periodically check that the frame is not damaged There is a risk of equipment damage Install the unit in a safe location where nobody can step on or fall onto it Do not install the unit on a defective stand There is a risk of unit and property damage Install the drain hose to ensure adequate drainage There is a risk of water leakage ...

Page 2: ...ilation products on the chassis of the unit Do not install the unit near high frequency generator sources Do not install in an area where the unit will be exposed to volatile organic compounds Installing in an Area Exposed to Unconditioned Air In some installation applications areas floors walls in some rooms may be exposed to unconditioned air The room may be above or next to an unheated garage o...

Page 3: ...strictions in the refrigeration components Do not over tighten flare nuts Excessive tightening will cause fittings to crack Insulate Refrigerant Pipes Sufficiently insulate all cold surfaces to prevent moisture forming All pipes must be insulated and each pipe must be separately wrapped Use field provided one half 1 2 inch thick or thicker closed cell insulation The thickness may need to be increa...

Page 4: ...fire electric shock explosion physical injury or death WARNING The information contained in this manual is intended for use by a trained electrician familiar with applicable local codes and the U S National Electric Code NEC and who is equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in personal injury or death Conn...

Page 5: ...d Communications Cable Terminals Optional Wired Wall Controller Installation Since the room temperature sensor is inside the remote controller to maintain proper space temperature install the remote controller in a place away from direct sunlight high humidity and direct supply of hot or cold air Install the remote controller about 5 ft above the floor in an area with good air circulation and an a...

Page 6: ...trations data information and other materials are the property of LG Electronics U S A Inc and are disclosed by LG Electronics U S A Inc only in confidence Due to our policy of continuous product innovation some specifications may change without notification LG Electronics U S A Inc Englewood Cliffs NJ All rights reserved LG is a registered trademark of LG Corp ...

Reviews: