13
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Nominal
Tons
Unit Model No. Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA
MOP Compressor
Quantity
Compressor
Motor RLA
(Cooling)
Condenser Fan Motor(s)
Condenser
Fan Quantity.
Condenser Fan
Motor FLA
3/4
LUU097HV
60 208 - 230
187 - 253
11.9
15
1
9.0
1
0.25
1
LUU127HV
12.3
1-1/2
LUU187HV
18.1
30
13.5
0.6
1-1/2
LUU189HV
20
30
13.5
1.6
2
LUU247HV
18.1
30
13.5
0.6
3
LUU367HV
24.5
40
18.0
2
0.6 x 2
3-1/2
LUU427HV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Table 4: Electrical Data.
Electrical Data
ELECTRICAL DATA