Outdoor
Indoor
Control terminal board
Cord
clamper
Cover control
A view
1
1
Main
power source
Switch box
Circuit Breaker
A
Control terminal board
Control box
Control box cover
(On which the Electric
Wiring Connection is put)
Main terminal board
Cord clamper
Connection
cord between
the indoor unit
and the
outdoor unit
Remote
control cord
15
ELECTRICALWIRING
Performthe
electricalwiring
workaccording
to
theelectrical
wiringconnection.
•All
wiringmust
complywith
local
requirements.
•Select
apower
sourcethat
iscapable
of
supplyingthe
currentrequired
bythe
air
conditioner.
• Use
arecognized
circuitbreaker
betweenthe
powersource
andthe
unit.
Adisconnection
deviceto
adequately
disconnectall
supplylines
mustbe
fitted.
•Capacity
ofcircuit
breaker
INDOORUNIT
•Remove
thecontrol
boxcover
for
electricalconnection
betweenthe
indoorand
outdoorunit.
(Removecrews)
€
•Use
thecord
clamperto
fixthe
cord.
WIRINGCONNECTION
OUTDOORUNIT
•Remove
thecontrol
coverfor
wiring
connection.
•Use
thecord
clamperto
fixthe
cord.
•Earthing
work
Connectthe
cableof
diameter1.6mm
2
ormore
tothe
earthingterminal
provided
inthe
controlbox
anddo
earthing.
Pleasecheck
!!
Capacity
MCB Rating (3 Phase)
36K BTU/h
51K BTU/h
66K BTU/h
90K BTU/h
102K BTU/h
132K BTU/h
198K BTU/h
264K BTU/h
25A
32A
32A
40A
50A
63A
80A
125A