–30–
Outdoor
Indoor
Control terminal board
Control box
Control box cover
(On which the Electric
Wiring Connection is put)
Main terminal board
Control terminal board
Cover control
A
A
view
Remote
control cord
Connection
cord between
the indoor unit
and the
outdoor unit
Cord clamper
1
1
Main
power source
Switch box
Circuit Breaker
Use a 35A(60K)
circuit breaker or time
delay fuse.
ELECTRICAL WIRING
INDOOR UNIT
• Remove the control box cover for electrical con-
nection between the indoor and outdoor
unit.(Remove two screws
➀
.)
• Use the cord clamper to fix the cord.
Perform the electrical wiring work according to the electrical wiring
connection.
• All wiring must comply with local requirements.
• Select a power source that is capable of supplying
the current required by the air conditioner.
• Use a recognized circuit breaker 35A(60K)
between the power source and the unit. A discon-
nection device to adequately disconnect all supply
lines must be fitted.
WIRING CONNECTION
OUTDOOR UNIT
• Remove the control cover for wiring connection.
• Use the cord clamper to fix the cord.
• Earthing work
Connect the cable of diameter 1.6mm
2
or more to
the earthing terminal provided in the control box
and do earthing.
Please check !!
Capacity
3 Phase
48K BTU/h
25A
60K BTU/h
25A