52 MPS Multi Air Conditioner
Installation
1. To remove the front panel from the indoor unit,
remove the front panel from the indoor unit cabinet.
■
Set the air direction louvers up-and-down to the posi-
tion(horizontally) by hand.
■
Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille
toward you and lift it off.
(9K Btu models: 2EA,
12K Btu models: 3EA)
2. To check the drainage.
■
Pour a glass of water on the evaporator.
■
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the
drain exit.
3. Drain piping
■
The drain hose should point downward for easy drain
flow.
■
Do not make drain piping.
1. Form the piping by wrapping the connecting por-
tion of the indoor unit with insulation material and
secure it with two kinds of vinyl tapes.
■
If you want to connect an additional drain hose, the
end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below
the indoor unit perform the following.
■
Tape the piping, drain hose and connecting cable
from down to up.
■
Secure the tapped piping along the exterior wall using
saddle or equivalent
3. In cases where the Outdoor unit is installed above
the Indoor unit perform the following.
■
Tape the piping and connecting cable from down to
up.
■
Secure the taped piping along the exterior wall. Form
a trap to prevent water entering the room.
■
Fix the piping onto the wall by saddle or equivalent.
Pull the right and
the left side.
Screw
• Trap is required to prevent water from entering
into electrical parts.
Plastic
band
Taping
Drain hose
Pipings
Connecting
cable
Power supply
cord
Seal a small
opening around
the pipings with
gum type sealer.
Seal a small opening
around the pipings
with gum type sealer.
Trap
Trap
Downward slope
Do not raise
Accumulated
drain water
Tip of drain hose
dipped in water
Air
Waving
Water
leakage
Water
leakage
Ditch
Less than
50mm gap
Water
leakage
(4) Checking the drainage
(5) Form the piping