Venting the Dryer (cont.)
routIng and connectIng ductWork
INCORRECT VENTINg
CORRECT VENTINg
NOTE
Deduct 6 ft. (1.8 m) for each additional elbow. Use of
more than four 90º elbows is not recommended.
NOTE
Follow the guidelines below to maximize drying
performance and reduce lint buildup and
condensation in the ductwork.
Ductwork and fittings are NOT included and must be
purchased separately.
• Use 4-inch (10.2 cm) diameter rigid or semirigid
metal ductwork.
• The exhaust duct run should be as short as possible.
• Use as few elbow joints as possible.
• The male end of each section of exhaust duct must
point away from the dryer.
• Use duct tape on all duct joints.
• Insulate ductwork that runs through unheated areas
in order to reduce condensation and lint buildup on
duct surfaces.
• Failure to exhaust the dryer correctly will void the
dryer’s warranty.
ductwork
WALL CAP TYPE
0
1
2
3
4
0
1
2
3
4
NUmBER OF
90° ELBOWS
mAXImUm LENgTH OF
4-INCH DIAmETER
RIgID mETAL DUCT
65 ft. (19.8 m)
55 ft. (16.8 m)
47 ft. (14.3 m)
36 ft. (11.0 m)
28 ft. (8.5 m)
55 ft. (16.8 m)
47 ft. (14.3 m )
41 ft. (12.5 m)
30 ft. (9.1 m)
22 ft. (6.7 m)
Recommended
Use only for
short run
installations
4”
(10.2 cm)
4”
(10.2 cm)
2
2
/
4
”
(6.35 cm)
INSTALLATION
MFL67731085_en_170711.indd 20
2017.7.11 4:4:54 PM
Summary of Contents for DLEX4370 Series
Page 48: ...MFL67731085_en_170711 indd 48 2017 7 11 4 5 26 PM ...
Page 96: ...MFL67731085_sp_170711 indd 48 2017 7 11 4 11 44 PM ...
Page 97: ...MFL67731085_sp_170711 indd 49 2017 7 11 4 11 44 PM ...
Page 98: ...MFL67731085_sp_170711 indd 50 2017 7 11 4 11 44 PM ...
Page 99: ...MFL67731085_sp_170711 indd 51 2017 7 11 4 11 44 PM ...