–8–
Refrigeration Cycle Diagram
• CV-H186BLB0
• CV-H246BLB0
For installation over rated distance, 30g of refrigerant should be added for each meter.
ex) If 18K or 24K Model is installed at a distance of 15m, 300g of refrigerant should be added.
(15-7.5) x 30g = 225g
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
HEAT
EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
CAPILLARY TUBE
COOLING
HEATING
REVERSING
VALVE
Pipe size(Diameter:ø)
Piping length(m)
Elevation(m)
MODEL
Gas
Liquid
Rated
Max
Rated
Max
CV-H186BLB0
1/2"
1/4"
7.5
15
5
8
CV-H246BLB0
5/8"
1/4"
7.5
20
5
8