ENGLISH
4
1.3 Warning Label
Product/warning label and Battery Control Unit’s traceability label are behind the front cover.
The front cover opens by turning the front cover handle counterclockwise. Battery Modules’
traceability labels are attached to the side of the Battery Modules.
1. Product/Warning Label
2. Traceability label
2-1. Battery Control Unit
2-2. Battery Module
EH153064P8S7DMA
○○○○○○○○○○
SH077064P8S7BMA
○○○○○○○○○○
A
SH077064P8S7BMA
○○○○○○○○○○
B
1.4 Qualifi ed Personnel
This guide for the tasks and procedures described herein is intended for use by skilled staff
only. A skilled staff is defi ned as a trained and qualifi ed electrician or installer who has all of
the following skills and experience:
• Knowledge of the functional principles and operation of on-grid and off -grid
(backup) systems
•
Knowledge of the dangers and risks associated with installing and using electrical
devices and acceptable mitigation methods
•
Knowledge of the installation of electrical devices
•
Knowledge of and adherence to this guide and all safety precautions and best
practices
• Qualifi cation specifi ed in battery warranty fi le
: BLG RESU-certifi cation in the battery website
: Knowledge of local installation standards
: Electrical license for battery installation required by the country or state
•
Repair the battery by disassembly is possible only at the LG Service Center or by
a person who is specially authorized separately from the installation qualifi cation
2 Product Introduction
2.1 Technical Data
2.1.1
Dimensions and Weight
BLG RESU10HP
Part Number
TLB00983101
Width
504 mm (19.8”)
Height
817 mm (32.2”)
Depth
295 mm (11.6”)
Weight
1)
111 kg (244 lbs)
1) Battery pack weights may vary slightly.
2.1.2 Performance
Electrical Characteristics
Usable Energy
1)
9.6 kWh
Battery Capacity
64.1 Ah
Voltage Range
350 to 450 VDC
Absolute Max. Voltage
595 VDC
Max. Current (charging/discharging)
14.3A @ 350V
Max. Power (charging/discharging)
5 kW
Peak Power
2)
(only discharging)
7 kW for 10 sec.
Peak Current (only discharging)
20.9 A for 10 sec.
Communication Interface
RS485/ CAN
DC Disconnect
Circuit Breaker
Connection Method
Spring Type Connector
User Interface
LEDs for Normal and Fault Operation
Operating Conditions
Installation Location
Indoor/Outdoor
Operating Temperature
charge
14°F to 122°F (-10°C to 50°C)
discharge
-4°F to 122°F (-20°C to 50°C)
Operating Temperature
(Recommended)
59°F to 86°F (15°C to 30°C)
Storage Temperature
-22°F to 140°F (-30°C to 60°C), acceptable for 7
days in total
-4°F to 113°F (-20°C to 45°C), acceptable for the
fi rst 6 months
-4°F to 86°F (-20°C to 30°C), acceptable for months
7~12
Humidity
5% to 95%
Altitude
Max. 6,562 ft (2,000 m)
Cooling Strategy
Natural Convection
Certifi cation
Safety
Cell
Battery
Pack
UL1642
CE / RCM / IEC 62619 / UL1973 /
IEC62477-1
Emissions
FCC
Hazardous Materials Classifi cation
Class 9
Transportation
UN38.3
Ingress Rating
IP55
※ Test Conditions: Temperature 25°C/77°F, at the beginning of life.
※ Energy is measured under specifi c conditions from LG Electronics (0.3CPCV/0.3CP).
1) Value for battery pack only. Maximal usable energy at the AC output may vary by condition,
such as inverter effi ciency, confi guration and temperature.
2) Peak current excludes repeated short duration (less than 10 sec. of current pattern).