LG BLGRESU10HP Installation Manual Download Page 2

19

4 Commissioning

4.1 LED Indicators

The LED indicators on the front of the battery pack show its operational state as follows:

LED 1

(Power)

LED 2

(Charge)

LED 3

(Discharge)

LED 4

(Fault)

Status

Power on (lnit)

-

-

-

Ready

Normal

-

-

Charge

-

-

Discharge

-

-

Fault 1

-

-

Fault 2

(Every 10 s)

-

-

-

Power-saving

-

-

-

-

Power Off

(Quickly)

-

-

-

Updating

FW Update

-

Update

Complete

-

Update Failed

There are four LED indicators on the front of the battery packs to show its operating status.

1. Power On(Init) : Initialization for operating the battery

2. Ready : Battery is ready for operating normally.

3. Charge : Battery pack is charging.

4. Discharge :Battery pack is discharging.

5. Fault : Battery pack is warning state. Fault1 is blinking. Fault 2 is continuous. See 

Section 5 Troubleshooting guide for detail condition.

6. Power saving : Battery stay in minimum self consumption power mode.

7. FW update : Battery is in update sequence. See the detail LED indication about 

Updating, Update complete, Update failed.

4.2 Powering On the Battery Pack

Power on the battery through the following steps:

1. Open the front cover.  

2. Ensure the circuit breaker switch is in the OFF position.

3. Turn on the circuit breaker.

4. Seconds after the circuit breaker switch is ON, four (4) LED indicators will light 

up.

5.

Ensure the LED power indicator is ON to confirm that the battery pack has 

successfully initialized. The LED power indicator on the front should be green. 

6. Close the front cover. 

7. Turn on the inverter.

CAUTION

If it stays off, indicates FAULT or fails to operate, do not use the battery pack and contact LG 

Electronics or your distributor.

4.3  Shutting Off the Battery Pack

Shut off the battery packthrough the following steps:

1.

Turn off the inverter.

2. Open the front cover.

3.

Turn off the battery pack by moving the circuit breaker switch to the OFF 

position.

4. Make sure that every LED indicator on the battery pack is OFF. (After 10 

seconds, the LED lights will turn off and the battery will shut down completely.)

5. Close the front cover.

5 Troubleshooting

5.1  Troubleshooting Overview

Check the LED indicators on the front to determine the state of the battery pack. A fault state 
is triggered when certain conditions like voltage or temperature are beyond design limitations. 
The battery pack’s BMS periodically reports its operating state to the inverter.

When the battery pack falls outside of prescribed limits, it enters a fault state. When a fault is 
reported, the inverter immediately terminates operation.

Use the monitoring software on the inverter to identify what caused the fault state. The possible 
warning messages are as follows:

Battery Overvoltage

Battery Undervoltage

Battery Over Temperature

Battery Under Temperature

Battery Discharge Overcurrent

Battery Charge Overcurrent

Battery Overcharge Power Limit

Battery Overdischarge Power Limit

BMS Internal Error

External Communication Error

Internal Communication Error

Battery Cell Deviation Voltage

Battery Pack Undervoltage

Battery Urgent Undervoltage

The fault state is cleared when the battery pack resumes normal operation. If battery pack is not 

working correctly and the issue persists, contact a qualified staff, Installer or LG Electronics 

regional contact service point.

NOTE

For serious warnings, if no proper corrective action is taken by the inverter, the battery 
pack’s circuit breaker will automatically trip to protect itself.

CAUTION

If the battery pack or the inverter indicates FAULT or fails to operate, contact LG 
Electronics regional contact point or your distributor immediately.

5.1.1  Post-Installation Checklist

Yes

No

1.

Visually check if the wiring matches the installation manual. (Section 
3.3 Cable Connections.)

2.

The circuit breaker is ON.

3.

The battery LED power indicator is ON.

4.

The inverter power is ON.

5.

The inverter has the latest firmware installed. 

1)

6.

The inverter recognizes the battery. 

2)

7.

The battery is operational after installation.

7-1. The AC grid is connected.

7-2. The meter is installed. 

7-3. Government approval is complete.

8.

IF ANY ITEM IN #7 IS CHECKED AS "NO" OR IF THE INVERTER  
NEEDS TO BE TURNED OFF, TURN OFF THE CIRCUIT 
BREAKER.

3)

Summary of Contents for BLGRESU10HP

Page 1: ...lectronics strongly advises users to exercise due care in following LGE s product installation manual A warranty claims are invalid if damage is caused by human error inconsistent with the installation manual MODEL LG HBP10H BLGRESU10HP Read in conjunction with Part 1 ...

Page 2: ...etely 5 Close the front cover 5 Troubleshooting 5 1 Troubleshooting Overview Check the LED indicators on the front to determine the state of the battery pack A fault state is triggered when certain conditions like voltage or temperature are beyond design limitations The battery pack s BMS periodically reports its operating state to the inverter When the battery pack falls outside of prescribed lim...

Page 3: ...er to the inverter s troubleshooting guide for battery setup instructions 2 If the inverter is connected to the internet collect the log files from the inverter company 2 1 Send the fault ID to LG Electronics regional contact point 2 2 Turn off the circuit breaker 2 3 Wait further instruction from LG Electronics 3 If the inverter is not connected to the internet check the inverter LCD to read the ...

Page 4: ... er In th e lin e HE RE Pl ac e th e sp ac er In th e lin e HE RE Pl ac e th e sp ac er In th e lin e HE RE Pl ac e th e sp ac er In th e lin e HE RE Battery Control Unit Spacer 11 After that place the second spacer on top of the Battery Modules Pla ce the spa cer In the lin e HE RE Pla ce the spa cer In the lin e HE RE Pla ce the spa cer In the lin e HE RE Pla ce the spa cer In the lin e HE RE Pl...

Page 5: ...phone Germany 0049 0 39484 976 380 Austria 0043 0 720 11 66 01 Switzerland 0041 0 44 505 11 42 Benelux 0031 0 20 225 1660 Email lge e service48 de Germany Corporation Address LG Electronics Deutschland GmbH Alfred Herrhausen Allee 3 5 65760 Eschborn Telephone 0049 0 18 06 807 020 Email b2b service lge de Benelux Corporation Address LG Electronics Benelux B V Krijgsman 1 1186 DM Amstelveen The Neth...

Page 6: ... check the battery status is as follows 1 RMD Wi Fi direct connection First proceed with RMD Wi Fi direct connection as shown below Search and access the SSID of the RMD AP from a device hereinafter referred to as a device supporting WLAN Station functions such as a smartphone RMD SSID has a structure of RESU_ or RMD RMD WLAN STM MAC ADDRESS For the devices below the SSID of the RMD SoftAP is RESU...

Page 7: ...Top cover assy and BMA Retrieve pack if issue occurs repeatedly BMS Internal Fault2 DiagResultHwFault2 0x0004 Try restarting the battery Retrieve pack if issue occurs repeatedly DiagResultHwFault2 0x1000 DiagResultFault2 0x10000 DiagResultHwFault2 0x0001 DiagResultHwFault2 0x0008 DiagResultHwFault2 0x0200 DiagResultHwFault2 0x0100 DiagResultHwFault2 0x0040 DiagResultHwFault2 0x0002 DiagResultHwFau...

Page 8: ...selected correctly click the Send button 6 If you check the success message in the upper right corner the update was successful 7 2 3 Installation via RMD for web user 7 2 3 1 User Agreement Visit https resumonitor lgensol com and Sign in A B C D E F G H Click Installation User Agreement and search the product which you will install Select your region Non EU EU Get the agreement of privacy policy ...

Page 9: ... password and click Register to go to the home screen The default password is set to 123456 and can be changed in the Web UI 7 2 3 4 Config setting 1 Server Use Decide whether to use connect to the cloud server 2 Inverter Type N A 3 BMA Number Select number of Modules Select 2 4 Communication Type N A 5 Country Select country 6 Time Zone Hour Option to display 1hour in UTC 7 Time Zone Minute Optio...

Page 10: ...lect the AP to access from the SSID combo box enter the password and click the Connect button Manual input is possible 4 If the connection to the AP is successful a pop up window informs whether the connection was successful as follows 7 2 3 6 Check the Installation Status Enter the Monitoring Server Tab Check the Status values are OK Whether the Ethernet connection or Wi Fi connection OK depends ...

Page 11: ......

Reviews: