INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
MODEL
CAPACITY
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
AVUQ36GM1A0
36 kBtu/h Ø 15,88 (5/8) Ø 9,52 (3/8)
7,5
50
0
30
20
AVUQ48GM2A0
46 kBtu/h Ø 15,88 (5/8) Ø 9,52 (3/8)
7,5
50
0
30
20
AVUQ60GM2A0
58 kBtu/h Ø 19,05 (3/4) Ø 9,52 (3/8)
7,5
50
0
30
20
Piping length and the elevation
Ceiling Suspended Air conditioner
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
• Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
CAUTION
!
If installed tube is shorter than 15 m, additional charging is not necessary.
Additional Refrigerant = (A -15) x Additional refrigerant (g)