- 2 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Specification
Cooling Capacity
kW
(Min~Rating~Max)
Btu/h.
Heating Capacity
kW
(Min~Rating~Max)
Btu/h.
Power Input
Cooling/Heating
W
Running Current
Cooling/Heating
A
Starting Current
Cooling/Heating
A
EER
W/W
Btu/h.W
COP
W/W
Power Supply
Ø / V / Hz
Power Factor
%
Air Flow Rate
Indoor,Max
m
3
/min(CFM)
Outdoor,Max
m
3
/min(CFM)
Moisture Removal
l/h.
Sound Level
Indoor,H/M/L
dB(A)±3
Outdoor,Max
dB(A)±3
Refrigerant & Charge(at 7.5 m)
g(oz)
Additional Refrigerant charge
g/m(oz/ft)
Compressor
Type
Model
Motor Type
Oil Type
Oil Charge
cc
O.L.P. name
Fan(Indoor)
Type
Motor Output
W
Fan(Outdoor)
Type
Motor Type
Motor Output
W
Circuit Breaker*
A
Power Supply Cable
No.*mm
2
Power and Transmission Cable
No.*mm
2
+No.*mm
2
Piping Liquid
Side
mm(in)
Connections
Gas Side
mm(in)
Drain Hose
O.D., I.D.
mm(in)
Dimensions
Indoor (W*H*D)
mm
inch
Outdoor (W*H*D)
mm
inch
Net Weight
Indoor
kg(lbs)
Outdoor
kg(lbs)
Operation Range
Cooling(Outdoor)
°C(°F)
Heating(Outdoor)
°C(°F)
Max. Piping Length
m(ft)
Max. Elevation Difference
m(ft)
Tool Code(Chassis)
Outdoor
Models
ASNW30GDGM0
AUUW306D
8
27297
9.6
32756
2,690/3,250
12.0/14.5
12.0/14.5
2.97
10.13
2.95
1 / 220 ~ 240 / 50
97
21(742)
58(2048)
3.5
48 /44/ 39
58
R410A, 1,800(63.3)(at 10m)
30(0.323)
Twin Rotary
5KD240XAE21
Brushless DC motor
FV50S
900
CS-7L 115
Cross Flow Fan
70
Propeller
Brushless DC motor
80
25
3*2.5
4*0.75
6.35(1/4)
15.88(5/8)
21.5, 16 (0.85, 0.63)
1,209*346*205
47.6*13.6*8.1
870*800*320
34.3*31.5*12.6
18(39.7)
60(132.3)
-10 ~ 43 (14 ~ 109.4)
-15 ~ 24 (5 ~ 75.2)
50(164)
30(98.4)
SD + UE1
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national
code.
3. The specification may be subject to change without notic for purpose
of improvement.
Summary of Contents for ASNW30GDGM0
Page 10: ...P NO MFL37468307 AUGUST 2009 ...