28
Room Air Conditioner
Installation
Evacuation
• Connect the charge hose end described in the
preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.
• When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and stop the
vacuum pump.
Finishing the job
• With a service valve wrench, turn the valve
stem of liquid side valve counter-clockwise to
fully open the valve.
• Turn the valve stem of gas side valve counter-
clockwise to fully open the valve.
• Loosen the charge hose connected to the gas
side service port slightly to release the pressure,
then remove the hose.
• Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut securely
with an adjustable wrench. This process is very
important to prevent leakage from the system.
• Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
(1) Remove the caps from the gas side and
liquid side valves.
(2) Remove the service-port cap from the gas
side valve.
(3) To open the gas side valve turn the valve
stem counterclockwise approximately 90°,
wait for about 2~3 seconds, and close it.
(4) Apply a soap water or a liquid neutral
detergent on the indoor unit connection or
outdoor unit connections by a soft brush to
check for leakage of the connecting points
of the piping.
(5) If bubbles come out, the pipes have
leakage.
Soap water method
Suction Line
Evaporator Line
Cap
Hexagonal wrench
3-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h
vacuum pump is used
10 min. or more
15 min. or more
If tubing length is less
than 10m (33 ft)
if tubing length is longer
than 10m (33 ft)
Indoor unit
Outdoor unit
Lo
Hi
Manifold valve
Vacuum pump
Pressure
gauge
Open
Close
Summary of Contents for AS-C0914DZ0
Page 32: ...32 Room Air Conditioner ...
Page 33: ...P No 3828A30087P ...