MULTI V S
Outdoor Unit
4. Electric Characteristics
14
Product Data
4.1 1 Phase / Heat Pump
■
50Hz
■
60Hz
Model
Unit
Power Supply
COMP
OFM
Hz
Volts
Voltage-range
MCA
TOCA
MFA
MSC
RLA(Cooling)
RLA(Heating)
kW
FLA
4 HP
50
220-240
Min.:198, Max.:264
25.0
26.0
30
-
17.8
13.5
0.12
1.0
5 HP
(1Fan)
50
220-240
Min.:198, Max.:264
27.5
26.0
30
-
24.0
17.6
0.12
1.0
5 HP
(2Fan)
50
220-240
Min.:198, Max.:264
27.5
26.0
30
-
20.5
18.5
0.35
1.0
6 HP
50
220-240
Min.:198, Max.:264
29.4
26.0
40
-
23.2
22.4
0.35
1.0
Model
Unit
Power Supply
COMP
OFM
Hz
Volts
Voltage-range
MCA
TOCA
MFA
MSC
RLA(Cooling)
RLA(Heating)
kW
FLA
4 HP
60
220
Min.:198, Max.:242
25.0
26.0
30
-
17.8
13.5
0.12
1.0
5 HP
(1Fan)
60
220
Min.:198, Max.:242
27.5
26.0
30
-
24.0
17.6
0.12
1.0
5 HP
(2Fan)
60
220
Min.:198, Max.:242
27.5
26.0
30
-
20.5
18.5
0.35
1.0
6 HP
60
220
Min.:198, Max.:242
29.4
26.0
40
-
23.2
22.4
0.35
1.0
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum
range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is recommended fuse amps.
9. TOCA is minimum required amperes for selecting the circuit breaker and ground fault
circuit interrupter. Please select the circuit breaker size equal or greater than TOCA.
All installation site must require attachment of an earth leakage breaker.[Circuit
breaker type is ELCB (Earth Leakage Circuit Breaker)].
10.Select the electrical equipment of combination unit according to the electrical
characteristics of individual unit.
Symbols
MCA :
Minimum Circuit Amperes (A)
TOCA :
Total Over Current Amperes (A)
MFA :
Maximum Fuse Amperes (A)
MSC :
Maximum Starting Current (A)
RLA :
Rated Load Amperes (A)
OFM :
Outdoor Fan Motor
kW :
Fan Motor rated output (kW)
FLA :
Full Load Amperes (A)
Summary of Contents for ARUN040GSS0
Page 3: ...General information MULTI V S Outdoor Unit 1 Model Line up External Appearance 2 Nomenclature ...
Page 98: ...93 MULTI V S Outdoor Unit Product Data 10 Wiring Diagrams 10 1 4 HP U4 Chassis 1Ø ...
Page 99: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 94 Product Data 10 2 5 HP U4 Chassis 1Ø ...
Page 100: ...10 Wiring Diagrams 95 MULTI V S Outdoor Unit Product Data 10 3 5 6 HP U3 Chassis 1Ø ...
Page 101: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 96 Product Data 10 4 4 5 6 HP 3Ø ...
Page 102: ...10 Wiring Diagrams 97 MULTI V S Outdoor Unit Product Data 10 5 8 HP 3Ø ...
Page 103: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 98 Product Data 10 6 10 12 HP 3Ø ...