Service Manual 63
Troubleshooting Guide
Electronic Parts (9k model)
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 115V, 60Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable
• Check PWB Ass'y(Outdoor unit)
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
• Connector related to CN-POWER
• Connector related to CN-FAN
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Ass'y Check
• Connector related to CN-DC/DC
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector(including connecting
cable of Indoor/Outdoor Unit)
PCB Board Operation Check
Items
• Power Transformer
(Outdoor unit)
- Input Voltage
- Output Voltage
• IC01D(7812) Output
(Indoor/Outdoor unit)
• IC02D(7805) Output (Indoor unit)
IC03D(7805) Output (Outdoor unit)
• IC01A(KIA7036, Reset IC)
OSC01B(4MHz)
(Indoor/Outdoor unit)
• Replace SMPS
Module
• Replace IC01D
• Replace
IC02D(Indoor unit)
IC03D(Outdoor unit)
• Replace faulty parts
- About AC115V±10% - Check the power voltage
- About DC15V±3
• DC +12V
• DC +5V
• Voltage of Outdoor unit Micom No. 18,
Voltage of Indoor unit Micom No. 43 and
soldering condition
Content
Remedy
NO
YES
(After 20 seconds)
Summary of Contents for ARTCOOL LAN091HNP
Page 48: ...48 Room Air Conditioner Schematic Diagram Heat Pump Series Cooling Only Series Outdoor Unit ...
Page 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM P No 6871A20921A PCB ASSEMBLY ...
Page 53: ...Service Manual 53 Schematic Diagram 2 Outdoor Unit Cooling Only Models Heating Models ...
Page 76: ...P No 3828A20926C December 2006 Printed in Korea ...