GENERAL DATA
Table 2: Art Cool Gallery Indoor Unit Electrical Data
Electrical
Unit Model Nos.
Nom.
Tons
Compressor
Qty
Compressor(A)
Cool/Heat
Fan Qty
ODU Fan(A)
IDU Fan(A)
MCA(A)
MOP(A)
Art Cool Premier
LAU090HVP
3/4
1
6.8/7.6
1
0.25
14.7
10
15
LAU120HVP
1
1
6.8/7.6
1
0.25
14.7
10
15
For component model nos.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity
ODU Fan = Outdoor Unit Fan Motor
IDU Fan = Indoor Unit Fan Motor
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.