28 | Product data
Art Cool
™
Mirror W
all Mounted Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Table 10: Summary Data—Central Controllers (Connect to optional PI-485 Terminals Internet A, Internet B).
Table 11: Summary Data—Integration Solutions (Connect to optional PI-485 Terminals Internet A, Internet B).
Before specifying or placing an order, refer to the V-net network Solutions Engineering Product Data Book, and review the detailed technical data provided to fully understand the capabilities and limitations of
these devices.
Before specifying or placing an order, refer to the V-net network Solutions Engineering Product Data Book, and review the detailed technical data provided to fully understand the capabilities and limitations of
these devices.
* BACnet
TM
is a trademark of ASHRAE; LonWorks
TM
is a trademark of Echlelon Corporation.
ACCeSSorieS
Central
Controller
name
Model no.
Devices
per
Controller
Systems
per Comm
Bus
Devices
per Comm
Bus
no. of
Comm
Bus
Ports
Binary
Signals
Input/
output
Power,
Conn
Description
AC Smart IV
PACS4B000
128
16
128
1
2 DI /
2 Do 24 VAC
Monitors / operates indoor units
through a touch screen. Manages
up to 128 devices. Advanced
functions include programmable
schedules, temperature setpoint
range lock, remote controller lock,
run time limit, manual control and
scheduling of digital output kit,
peak/demand control, visual floor
plan navigation, web access,
operation and error history log, one
digital input and two digital outputs
for device interlocking and error
e-mail notification.
AC Ez
PQCSZ250S0
32
16
256
1
---
12 VDC,
oDU
Provides for scheduling in addition
to basic indoor unit control and
monitoring.
Advanced
Control
Platform IV
(ACP IV)
PACP4B000
256
16
64
4
10/4 24 VAC
Provides for scheduling, remote
controller lock, setpoint range limit,
web access, peak/demand control,
PDI integration, and AC Manager
Plus integration advanced
functionality in addition to basic unit
control and monitoring.
Integration
Solution
name
Model no.
Devices
per
Controller
Systems
per
Comm
Bus
Devices
per Comm
Bus
no. of
Comm
Bus
Ports
Power
Binary
Signals
Input/
output
Description
ACP IV
BACnet
®
Gateway*
PQnFB17C1
256
16
256
4
24 VAC
10/4
Allow integration of LG equipment
for control and monitoring by open
protocol BACnet
TM
and
LonWorks
TM
building automation
and controls systems.*
LonWorks
®
Gateway*
PLnWKB100
64
16
64
1
24 VAC