DIP Switch Setting
Indoor Unit
Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start
automatically with the improved speed by turning the DIP switch #3 of the outdoor unit and
resetting the power.
* Specific conditions:
- All names of the indoor units are ARNU****4
- The serial number of Multi V super IV (outdoor units) is after October 2013,
28
ENGLISH
INSTALLATION
CAUTION
!
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function
Description
Setting Off
Setting On
Default
SW1 Communication N/A (Default)
-
-
Off
SW2 Cycle
N/A (Default)
-
-
Off
SW3 Group Control
Selection of Master
or Slave
Master
Slave
Off
SW4
Dry Contact
Mode
Selection of Dry
Contact Mode
Wired/Wireless remote
controller
Selection of Manual or
Auto operation Mode
Auto
Off
SW5 Installation
Fan continuous
operation
Continuous operation
Removall
-
Off
SW6 Heater linkage
N/A
-
-
Off
SW7
Ventilator
linkage
Selection of
Ventilator linkage
Linkage Removal
Working
Off
Vane selection
(Console)
Selection of up/down
side Vane
Up side + Down side
Vane
Up side Vane
Only
Region selection
Selection tropical
region
General model
Tropical model
SW8 Etc.
Spare
-
-
Off
DIP switch 7 segment
Outdoor Unit PCB
Outdoor Unit DIP Switch