Installation Manual
19
ENGLISH
How to Set E.S.P?
Note :
1. The above table shows the correlation between the air rates and E.S.P.
Setting Value
60
6.02
2.25
0.61
-
-
65
6.95
3.32
0.73
0.54
0.48
70
7.69
5.16
1.19
0.65
0.56
75
8.46
6.93
2.42
0.77
0.63
80
9.5
7.37
3.4
0.87
0.72
85
10.35
8.72
5.33
1.35
0.88
90
10.81
9.66
6.75
3.15
0.98
95
11.57
10.31
8.56
4.73
1.03
100
12.58
11.22
9.75
7.46
2.31
105
13.31
12.27
10.89
8.64
5.01
110
14.2
13.24
12.15
10.49
7.7
115
14.82
13.92
12.64
11.16
9.48
0(0)
1(10)
2(20)
3(30)
4(40)
Static Pressure(mmAq(Pa))
Setting Value
65
10.07
6.9
0.82
-
-
70
11.39
8.49
2.2
-
-
75
12.01
9.79
4.2
-
-
80
13.21
11.03
5.92
0.92
-
85
14.24
12.36
9.41
2.1
-
90
15.04
13.34
10.8
5.29
1.01
95
16.02
14.63
12.5
7.59
1.34
100
17.11
15.56
13.66
11.53
5.35
105
17.99
16.53
15.17
12.35
7.67
110
19.04
17.71
16.22
14.23
10.45
115
19.77
18.62
17.1
15.23
13.25
120
20.94
19.92
18.56
16.98
14.66
125
21.97
20.56
19.25
17.68
16.06
130
22.83
21.98
20.75
19.32
17.73
0(0)
1(10)
2(20)
3(30)
4(40)
Static Pressure(mmAq(Pa))
ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2
ARNU18GB2G2, ARNU24GB2G2
(Unit: CMM)
(Unit: CMM)