COIL CONTROL
SENSOR SETTINGS
The Coil Control Menus allows the user to view and adjust cycle period which is
related to control Target Pressure, and reheat Coil EEV
MAIN COIL CONTROL
This screen allows to change the target pressure change time period and unit (%,
pressure)
REHEAT COIL CONTROL
This screen allows to change EEV Control cycle and unit(%, EEV)
The Sensor Settings Menus allows the user to view and adjust Sensor installation
status and sensor specification(min/max value)
SUPPLY SENSORS
This screen allows to set the 3
rd
party sensor installation status(installed / Not
installed) and Min/Max value of sensor
Note:
Only Available at 0~10Vdc Type Temperature sensor. The minimum/maximum
values specified in the sensor manufacturer and those value must be entered or
wrong pressure level can be read.
SPACE SENSORS
This screen allows to set the 3
rd
party sensor installation status(Installed / Not
installed) and Min/Max value of sensor (if equipped, 0~10Vdc Type Temp Sensor)
Note:
The minimum/maximum values specified in the sensor manufacturer must be entered
if equipped 0~10Vdc Type Sensor.
Except, NTC type temperature sensor is installed (LG guide: MAMAC/ST-203-
EX120)
DIFFERENTIAL PRESSURE SENSORS
This screen allows to set the 3
rd
party differential sensor installation status and
maximum value for Exhaust fan air volume(CFM) control
-
Supply Differential Sensor (Default)
-
Exhaust Differential Sensor (Option, 3
rd
party)
Note:
The maximum values specified in the sensor manufacturer must be entered
CO
2
SENSORS
This screen allows to set the 3
rd
party CO
2
sensor installation status
Note:
The maximum values specified in the sensor manufacturer must be entered if
equipped with 0~10Vdc Type Sensor. If LG guided sensor is installed (Honeywell,
C7232A1008), do not need to set up Min/Max value.