ENERGY RECOVERY WHEEL STATUS (RTD only)
This screen provides overall status of the energy recovery wheel.
REFRIGERANT STATUS 1
The screen displays the refrigerant In / Out Temperature of Main Coil #1 and #2
* CTD model Only display Main Coil #1 Status
REFRIGERANT STATUS 2
The screen displays the refrigerant In / Out Temperature of Reheat Coil and
Recovery Coil
* CTD model Only display Reheat Coil Status
DEHUMIDIFICATION
This screen will display the overall dehumidification status and selected
dehumidification control mode.
The following dehumidification modes are available when the space is in occupied
mode:
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode
.
HGRH RAMP
This screen will display the status of the hot gas reheat ramp. The screen includes
the active set point, supply air discharge temperature, the ramp status, and hot gas
reheat valve request being sent from the controller.
RECOVERY COIL RAMP (RTD only)
This screen will display the status of the hot gas reheat ramp. The screen includes
the active set point, supply air discharge temperature, the ramp status, and hot gas
reheat valve request being sent from the controller.
CONDITIONS
The Space conditions are active when space temperature or humidity sensor is
installed and set enabled in controller. The enthalpy and dew point are calculated
based on the temperature and humidity readings. The unit altitude is used for the
enthalpy calculation.
15