INSTALLATION OF UNIT

9

E

N

G

L

IS

H

Installation Method

No.

Installation works

Descriptions

1

Preparation of tools and installation parts

Preparation of installation

2

Flaring the pipes

To insert the flare nuts, mounted on the con-

nection parts of both indoor and outdoor unit,

onto the copper pipes.

3

Pipe bending

To insert the flare nuts, mounted on the con-

nection parts of both indoor and outdoor unit,

onto the copper pipes.

4

Connection of installation parts (elbows,

socket etc)

To reduce the flow resistance of refrigerant.

5

Tighten the flare nut (outdoor)

Connection of long piping

6

Blowing the pipings

Connecting the pipings of the outdoor unit.

7

Tighten the flare nut (indoor)

To remove dust and scale in working.

8

Check a gas-leakage of the connecting part of

the pipings.

Connecting the pipings of the indoor unit.

9

Vacuum drying of the piping and indoor unit

10

Open the 3-way (liquid side) and 3-way (gas

side) valves.

The air which contains moisture and which re-

mains in the refrigeration cycle may cause a

malfunction on the compressor

11

Form the pipings

12

Checking the drainage (indoor unit)

To prevent heat loss and sweat

13

Connecting the cable between outdoor and

indoor unit

To ensure if water flow drain hose of indoor

unit.

14

Connecting the main cable to outdoor unit

Preparation of the operating

15

Supply the power to the crankcase heater

(Before the operating the unit)

16

Cooling operation (Use the remote control or

display of the indoor unit)

To prevent the liquid back to the compressor.

(Heat pump only)

Summary of Contents for APNC488TLA0

Page 1: ...ase read this installation manual completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly ENGLISH ...

Page 2: ...irection of the air flow vertically or horizontally to circulate indoor air Speed up the fan to cool or warm indoor air quickly in a short period of time Open windows regularly for ventilation as the indoor air quality may deteriorate if the air con ditioner is used for many hours Clean the air filter once every 2 weeks Dust and impurities collected in the air filter may block the air flow or weak...

Page 3: ... a defective or underrated circuit breaker Use this appliance on a dedicated circuit There is risk of fire or electric shock For electrical work contact the dealer seller a qualified electrician or an Authorized Service Center Do not disassemble or repair the product There is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the ...

Page 4: ...fter installation or repair of product Low refrigerant levels may cause failure of product Install the drain hose to ensure that water is drained away properly A bad connection may cause water leakage Keep level even when installing the product To avoid vibration or water leakage Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods It may cause...

Page 5: ...rts and tools 11 Plumbing materials and storage meth ods 12 Nitrogen substitution method 13 Preparation of Piping 14 Connection of piping 14 Precautions in bending 15 Form the Piping 15 Connecting the Cable to Indoor Unit 16 Connecting the cables to the outdoor unit 17 Power Supply and Wiring 18 Vacuum Drying of the Connecting Pipes and the Indoor Unit 19 Checking the Drainage 20 FINAL CHECK AND T...

Page 6: ...y Ensure the spaces indicated by arrows from the wall ceiling or other obstacles The indoor unit must keep the maintenance space 40 cm 40 cm 5 cm 100 cm Fence or obstacles More than 50 cm More than 50 cm More than 50 cm More than 100 cm Sunroof Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restr...

Page 7: ...levation A B Indoor unit Outdoor unit ATTENTION Capacity is based on standard length and maximum allowance length is on the basis of reli ability MODEL PIPE SIZE mm inch Max Length A m Max Elevation B m GAS SIDE LIQUID SIDE 48 k Ø15 88 5 8 Ø9 52 3 8 50 30 ...

Page 8: ...ng length exceeds 7 5 meters additional charge is required ac cording to the following table Example In case of 10 m long pipe one way the amount of refrigerant to be replenished is 10 7 5 x 25 62 5 g MODEL REFRIGERANT CHARGE 48 k Btu h 25 per 1 m Unit g The Indoor Unit Installation 1 The mounting floor should be strong and solid enough to prevent it from vibration 2 Drill the piping hole with 70 ...

Page 9: ...e flare nut indoor To remove dust and scale in working 8 Check a gas leakage of the connecting part of the pipings Connecting the pipings of the indoor unit 9 Vacuum drying of the piping and indoor unit 10 Open the 3 way liquid side and 3 way gas side valves The air which contains moisture and which re mains in the refrigeration cycle may cause a malfunction on the compressor 11 Form the pipings 1...

Page 10: ... amount 11 Bombe R410A Gas charge Cleaning the pipe 12 Spanner To tighten the connecting parts of the pipings 13 Monkey spanner 14 Driver Cutting the wires 15 Benchi 150 mm To measure the length 16 Tapeline To make holes through the concrete wall and blocks 17 Core drill 18 Voltmeter Amperemeter Clampmeter To measure the current and voltage 19 Insulation resistance tester To measure the insulation...

Page 11: ... of the compressor Do not cold and warm Clogging of EEV Capillary Gas shortages Degradation of refrigerant oil Poor insulation of the compressor Do not cold and warm Coun termea sure No moisture in the pipe Until the connection is completed the plumbing pipe entrance should be strictly controlled Stop plumbing at rainy day Pipe entrance should be taken side or bottom When removal burr after cuttin...

Page 12: ...en the internal pressure in pipe is abo ve the atmospheric pressure pinhole is o ccurred and it is a leakage cause Oxide scale Nitrogen CAUTION Always use the nitrogen not use oxygen carbon dioxide and a Chevron gas Please use the following nitrogen pressure 0 02 MPa Oxygen Promotes oxidative degradation of refrigerant oil Because it is flammable it is strictly prohibited to use Carbon dioxide Deg...

Page 13: ...ough Pipe Reamer Point down Flare nut Copper tube Bar Copper pipe Clamp handle Red arrow mark Cone Yoke Handle Bar A Inclined Inside is shining without scratches Smooth all round Even length all round Surface damaged Cracked Uneven thickness Improper flaring Copper tube 90 Slanted Uneven Rough Pipe Reamer Point down Flare nut Copper tube Bar Copper pipe Clamp handle Red arrow mark Cone Yoke Handle...

Page 14: ...of the chassis 2 Replace the tubing holder into original posi tion 3 Route the tubing and the drain hose staight backwards 4 Insert the connecting cable into the indoor unit through the hole Do not connect the cable to the indoor unit Make a small loop with the cable for easy connection later 5 Tape the tubing and the connecting cable 6 Indoor unit installation 7 Connecting the pipings to the indo...

Page 15: ...all with saddle or bracket Connecting the Cable to In door Unit In order to protect cable it should be in serted Bushing Rubber The inside and outside connecting cable can be connected after opening the inlet grille 1 Open the inlet grille manually Fig 1 2 Open the control cover with Driver 3 Connect the cables LG does not supply to the terminal block in the control box 4 Secure the control cover ...

Page 16: ...anel Right to the original position with the screw Over 5mm Round pressure terminal Power wire R Connected to indoor unit Power Input Outdoor unit 3Phase model Normal S T N 1 L 1 L 2 N Terminal Block Indoor 3 2 N 3 4 5 Perform grounding This product should be grounded Defective grounding could cause an electric shock CAUTION Over 5mm Round pressure terminal Power wire R Connected to indoor unit Po...

Page 17: ...burn out of the wires See to it that the starting voltage is main tained at more than 90 percent of the rated voltage marked on the name plate The following troubles would be caused by voltage drop down Vibration of a magnetic switch damage on the contact point there of fuse break ing disturbance to the normal function of a overload protection device 2 Wiring After the confirmation of the above co...

Page 18: ...the service port nut and connect the gauge manifold and the vacuum pump to the service port by the charge hose 4 Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 76 cmHg 5 Remove the valve stem nuts and fully open the stems of the 2 way and 3 way valves with a hexagon wrench 6 Tighten the valve stem nuts of the 2 way valve and 3 way valve 7 Disconnect the ...

Page 19: ...g the Drainage 1 Remove the inlet grille with your hands as shown right and left and pull in the direction indi cated by the arrow 2 Check the drainage Pour a glass of water into the drain pan Ensure if water flows drain hose of indoor unit ...

Page 20: ...repare the running test as follows Connect compound gauges to the check joints at discharge and suction sides of the compres sor Turn all switches OFF Turn the main switch ON Running test should be accomplished as follows Set operation switch at FAN and the fan will start Check to ensure that the fan sounds nor mal Next set it at COOL and the compressor will start Check to ensure that the compress...

Page 21: ...vent damage from localized heavy rain and avoid frequent flooded area If you can t meet above guide line in the seaside installation please contact LG Electronics for the additional anticorro sion Periodic more than once year clean ing of the dust or salt particles stuck on the heat exchanger by using water CAUTION Air conditioners should not be installed in areas where corrosive gases such as aci...

Page 22: ...22 ENGLISH ...

Page 23: ......

Reviews: