22
PRODUCT DATA
ENGLISH
External Static Pressure & Air Flow
- Air handler units are UL Listed up to 0.5 in.wc external static pressure, including air filter, set
coil, unless otherwise noted.
- in.wc = inch Water Column, inAq
High static pressure is 0.3 in.wc (Factory set Default)
Low static pressure is 0.1 in.wc
- If you set ESP incorrectly, the air conditioner may cause cooling & heating capacity down and
malfunction.
* : Max setting is only available for ANNQ60GKA4.
PRODUCT DATA
Flow rate
(CFM)
Setting Value @ ESP(in.wc)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Max (1 750)*
90
95
100
105
-
-
-
-
-
-
High (1 400)
77
82
87
94
100
102
106
110
116
116
Middle (1 260)
70
77
83
90
96
98
104
108
114
116
Low (1 000)
61
67
75
82
88
94
100
104
112
116