background image

- 2 -

Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

1. Specification

Note:

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F)

- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F)

Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB

- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB

Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)

- Level Difference of Zero

2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4. For more Capacity(*),refer to the combination table

Conversion Formula
kW = Btu/h class X 0.0002931
cfm = CMM x 35.3

Power Supply

Ø / V / Hz

Capacity(*)

Btu/h class

Current

Running Current

A

Fan

Motor Type

Fan Type

Motor Output(W) x No. of Unit

Air Flow Rate

CMM

(H / M / L)

CFM

External Static Pressure

mmAq

Capacitor

µF / Vac

Drive

Coil

Row x Column x FPI

Dimensions Body

mm(inch)

(W x H x D)

Decorative Panel

mm(inch)

Net Weight

Body

kg (lbs)

Decorative Panel

kg (lbs)

Air Filter

Sound Level (H / M / L)

dB(A)+3

Piping

Liquid

mm (inch)

Connections

Gas

mm (inch)

Drain(OD/ID)

mm(inch)

Dehumidification Rate

l/h

Safety Devices

Temperature Sensor

Referigerant

Referigerant Control

Transmission Interunit Cable

No. x AWG

Model

AMNW09GDER0[LMAN095HV]

AMNW12GDER0[LMAN125HV]

Indoor unit type

ART COOL Mirror

1/ 208~230/ 60

1/ 208~230/ 60

9,000

12,000

0.15

0.15

BLDC

BLDC

Cross Flow Fan

Cross Flow Fan

7.8 x 1

7.8 x 1

8.0/7.0/5.0

10.0/8.0/6.0

282/247/177

353/282/212

-

-

-

-

Direct Drive

Direct Drive

2R x 15C x 18

2R x 15C x 18

915 x 282 x 165 (36 x 11 3/32 x 6 1/2) 915 x 282 x 165 (36 x 11 3/32 x 6 1/2)

-

-

9.5(20.9)

9.5(20.9)

-

-

Long life filter

Long life filter

31/26/22

35/28/24

6.35 (1/4)

6.35 (1/4)

9.52 (3/8)

9.52 (3/8)

20/16 (0.787/0.630)

20/16 (0.787/0.630)

1.2

1.5

Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor

Thermistor

Thermistor

R410A

R410A

EEV(in Outdoor unit)

EEV(in Outdoor unit)

4X18(Including Earth)

4X18(Including Earth)

Summary of Contents for AMNW09GDER0

Page 1: ...UAL Exploded View MODEL AMNW09GDER0 LMAN095HV AMNW12GDER0 LMAN125HV CAUTION Before Servicing the unit read the safety precautions in Standard SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Page 2: ... Static Pressure mmAq Capacitor µF Vac Drive Coil Row x Column x FPI Dimensions Body mm inch W x H x D Decorative Panel mm inch Net Weight Body kg lbs Decorative Panel kg lbs Air Filter Sound Level H M L dB A 3 Piping Liquid mm inch Connections Gas mm inch Drain OD ID mm inch Dehumidification Rate l h Safety Devices Temperature Sensor Referigerant Referigerant Control Transmission Interunit Cable ...

Page 3: ...r operation High ceiling operation Hot start O O Reliability Self diagnosis O O Soft dry operation O O Auto changeover X X Auto cleaning O O Auto operation artificial intelligence O O Auto restart operation O O Child lock Convenience Energy Saving Cooling Mode X X Forced operation O O Group control Sleep mode O O Timer on off O O Timer weekly Two thermistor control Wide wired remote controller Del...

Page 4: ...ing Diagrams Heat exchanger Th3 Th1 Gas pipe connection port flare connection Th2 Liquid pipe connection port flare connection C F F Cooling Heating LOC Description PCB Connector Th1 Thermistor for Inlet air temperature CN_TH1 Th2 Thermistor for Liquid line temperature CN_TH1 Th3 Thermistor for Gas line temperature CN_TH2 ...

Page 5: ...ght 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 4 Wiring Diagrams CN_TH1 CN_DISP3 CN_OPTION CN_12V CN_U D CN_MOTOR CN_L R CN_CC CN_HVB CN_DISP1 CN_TH2 ...

Page 6: ...147582 146811A 135516 146811B 146811B 263230A 268711L 268711K 35211B W6640A 268711C 263230B 263230C 135311 354211 149304 249951 342800 266090 149303 346810 Indoor Air Thermistor Evaporater Thermistor TH2 WH Evaporater Thermistor TH3 RD 268711E 159830 Note Please ensure GCSC since the replacement parts may be changed depending upon the buyer s request Please check the correct parts in View RPL Repl...

Page 7: ...P NO MFL61777604 February 2009 ...

Reviews: