background image

- 2 -

Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

1. Specification

Indoor

Power Supply

Ø / V / Hz

Cooling Capacity

kW

Btu/h

Heating Capacity

kW

Btu/h

Current

Nominal Running Current

A

Fan

Motor Type

Fan Type

Motor Output(W) x No. of Unit

Air Flow Rate

CMM

(H / M / L)

cfm

External Static Pressure

mmAq

Capacitor

μF / Vac

Drive

Coil

Row x Column x FPI

Dimensions Body

mm(inch)

(W x H x D)

Decorative Panel

mm(inch)

Net Weight

Body

kg (lbs)

Decorative Panel

kg (lbs)

Air Filter

Sound Level (H / M / L)

dB(A)+3

Piping

Liquid

mm (inch)

Connections

Gas

mm (inch)

Drain(OD/ID)

mm

Dehumidification Rate

l/h

Safety Devices

Temperature Sensor

Referigerant

Referigerant Control

Connectable Outdoor Unit

Power and Transmission Interunit Cable

No.x mm

2

Indoor Unit Type

Model

Free Joint Multi

AMNH05GTRAO

AMNH07GTRA0

1/220~240/50

1/220~240/50

1.47

2.05

5,000

7,000

1.67

2.34

5,700

8,000

0.35

0.35

BLDC

BLDC

Turbo Fan

Turbo Fan

25*1

25*1

7.5/6/5

7.5/6/5

265/212/177

265/212/177

-

-

-

-

Direct Drive

Direct Drive

1R x 8C x 18

1R x 8C x 18

570*570*214(22.4*22.4*8.4)

570*570*214(22.4*22.4*8.4)

700*700*30(27.6*27.6*1.2)

700*700*30(27.6*27.6*1.2)

13(28.7)

13(28.7)

3(6.6)

3(6.6)

Long Life Filter

Long Life Filter

31/27/23

31/27/23

6.35(1/4)

6.35(1/4)

9.52(3/8)

9.52(3/8)

32/25

32/25

1.1

1.1

Fuse, Thermal Protector for Fan Motor

Fuse, Thermal Protector for Fan Motor

Thermistor

Thermistor

R410A

R410A

EEV(in Outdoor Unit or BD Unit)

EEV(in Outdoor Unit or BD Unit)

Multi F/FDX series

Multi F/FDX series

4*0.75

4*0.75

Note:

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB

- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB

Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB

- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB

Piping Length - Interconnecting Piping Length 7.5m

- Level Difference of Zero

2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Conversion Formula

kW  = Btu/h x 0.0002931

cfm = CMM x 35.3

Summary of Contents for AMNH05GTRA0

Page 1: ...er SVC MANUAL Exploded View CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com MODEL AMNH05GTRA0 AMNH07GTRA0 ...

Page 2: ...Fan Turbo Fan 25 1 25 1 7 5 6 5 7 5 6 5 265 212 177 265 212 177 Direct Drive Direct Drive 1R x 8C x 18 1R x 8C x 18 570 570 214 22 4 22 4 8 4 570 570 214 22 4 22 4 8 4 700 700 30 27 6 27 6 1 2 700 700 30 27 6 27 6 1 2 13 28 7 13 28 7 3 6 6 3 6 6 Long Life Filter Long Life Filter 31 27 23 31 27 23 6 35 1 4 6 35 1 4 9 52 3 8 9 52 3 8 32 25 32 25 1 1 1 1 Fuse Thermal Protector for Fan Motor Fuse Ther...

Page 3: ...High ceiling operation Hot start Reliability Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto elevation Grille Auto operation Artificial intelligence Auto restart operation Convenience Child lock Forced operation Group control Sleep mode Timer On Off Timer weekly Two thermistor control Standard wired remote controller Wide wired remote controller Deluxe wired remote controller ...

Page 4: ...eat exchanger Gas pipe connection port flare connection Liquid pipe connection port flare connection Cooling Heating Turbo fan Th3 Th1 Th2 LOC Description PCB Connector Th1 Thermistor for sunction air temperature CN TH1 Indoor Th2 Thermistor for evaporator inlet temperature Th3 Thermistor for evaporator outlet temperature CN TH2 Indoor ...

Page 5: ... CN D PUMP CN D PUMP CN POWER CN POWER CN VANE2 CN VANE2 CN VANE1 CN VANE1 CN DISPLAY CN DISPLAY CN MOTOR1 CN MOTOR1 CN REMO CN REMO CN FLOAT CN FLOAT CN ROOM CN ROOM CN OPTION CN OPTION CN PIPE IN CN PIPE IN CN PIPE OUT CN PIPE OUT CN D PUMP CN POWER CN VANE2 CN VANE1 CN DISPLAY CN MOTOR1 CN REMO CN FLOAT CN ROOM CN OPTION CN PIPE IN CN PIPE OUT ...

Page 6: ...uyer Øs request Please check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http biz Lgservice com 130411 131410 354211 148000 346810 352150 249310 267110 352116 263230B Eva in sensor 550140 263230C Eva out sensor 349600 W49810 W48300 249941 330871B 330871A 349480 W50060 W3110 359012 140570 130911B 158591 130911A 249951 268711C 268711B 263230A Air Inlet sensor 135511 2660...

Page 7: ...l Accessory Model PT UQC 135316 159830 749740B 749740A 135800 135303 146811 237202 145200 268711 135500 147581 266001 Note Please ensure GCSC since the replacement parts may be changed depending upon the buyer s request Please check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http biz Lgservice com ...

Page 8: ...P NO MFL48188405 NOVEMBER 2009 ...

Reviews: