38
INSTALLATION OF UNIT
ENGLISH
Display
Title
Cause of Error
Outdoor unit related error
1 0 4 2
Communication Error between Master
and Slave (For 20/25RT Only)
Failing to receive Slave signal at main PCB of
Master
1 0 5
1 Master Fan PCB Communication Error
Failing to receive fan signal at main PCB of unit.
2
Slave Fan PCB Communication
Error (For 20/25RT Only)
Failing to receive fan signal at main PCB of unit.
1 0 6
1 Master FAN IPM Fault Error
Instant Over Current at Master Fan IPM
2
Slave FAN IPM Fault Error (For
20/25RT Only)
Instant Over Current at Slave Fan IPM
1 0 7
1 Master Fan DC Link Low Voltage Error
Master Fan DC Link Input Voltage is abnormal
2
Slave Fan DC Link Low Voltage
Error (For 20/25RT Only)
Slave Fan DC Link Input Voltage is abnormal
1 1 3
1 Eva inlet pipe Temperature Sensor Error
Eva inlet pipe temperature sensor of Master is open or
short
2
Eva inlet pipe Temperature Sensor Error
(For 20/25RT Only)
Eva inlet pipe temperature sensor of Master is open or
short
1 1 5
1
Eva outlet pipe Temperature Sensor
Error
Eva outlet pipe Temperature Sensor open or short
2
Eva outlet pipe Temperature Sensor
Error (For 20/25RT Only)
Eva outlet pipe Temperature Sensor open or short
1 5 1
1
Failure of operation mode conversion at
Master
Pressure unbalance between Masters
2
Failure of operation mode conversion at
Slave (For 20/25RT Only)
Pressure unbalance between Slaves
1 7 3
1
Master Constant Speed Compressor
Fault
Comp locking, Check Valve leakage, comp dielectric
break down at Master
2
Slave Constant Speed Compressor Fault
(For 20/25RT Only)
Comp locking, Check Valve leakage, comp dielectric
break down at Slave
1 8 2
1
Master Main PCB Main-Sub Micom
communication error
Master Main PCB Main-Sub Micom communication
failed
2
Slave Main PCB Main-Sub Micom
communication error (For 20/25RT
Only)
Slave Main PCB Main-Sub Micom communication
failed
1 9 3
1
Excessive increase of Master Fan PCB
Heat Sink Temperature
Master Fan Inverter PCB Temperature is Over 95°C
2
Excessive increase of Slave Fan
PCB Heat Sink Temperature (For
20/25RT Only)
Slave Fan Inverter PCB Temperature is Over 95°C
1 9 4
1
Master Fan PCB Heat Sink Temperature
Sensor Error
Master Fan PCB Heat Sink Temperature Sensor open or
short
2
Slave Fan PCB Heat Sink
Temperature Sensor Error (For
20/25RT Only)
Slave Fan PCB Heat Sink Temperature Sensor
open or short