Single Package
34
_ 50Hz, R410A
Single Package
10. Performance data
Evaporator Fan Performance Data AK-H1808C02 (SI)
External Static Pressure(mm Aq.)
l/s
2.54
5.08
7.62
10.16
12.7
15.24
17.78
20.32
22.86
25.4
27.94
30.48
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW
565
597
636
680
731
0.08
0.37
0.72
1.12
1.57
591
624
662
707
758
0.32
0.61
0.95
1.35
1.81
618
650
689
733
784
0.50
0.79
1.13
1.53
1.99
644
677
715
760
811
0.65
0.94
1.28
1.68
2.14
671
703
742
786
837
0.78
1.07
1.42
1.82
2.27
697
730
768
813
864
0.91
1.20
1.54
1.94
2.40
724
756
795
839
890
1.02
1.31
1.65
2.05
2.51
750
783
821
866
917
1.12
1.41
1.75
2.15
2.61
777
809
848
892
943
1.22
1.51
1.85
2.25
2.71
803
836
874
919
970
1.31
1.60
1.94
2.34
2.80
830
862
901
945
996
1.40
1.69
2.03
2.43
2.89
856
889
927
972
1023
1.48
1.77
2.11
2.51
2.97
2077
2336
2596
2856
3115
External Static Pressure(mm Aq.)
l/s
33.02
35.56
38.1
40.64
43.18
45.72
48.26
50.8
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW
883
915
954
998
1049
1.56
1.85
2.19
2.59
3.05
909
942
980
1025
1076
1.64
1.93
2.27
2.67
3.13
936
968
1007
1051
1102
1.71
2.00
2.35
2.75
3.20
962
995
1033
1078
1129
1.78
2.07
2.42
2.82
3.27
989
1021
1060
1104
1155
1.85
2.14
2.49
2.89
3.34
1015
1048
1086
1131
1182
1.92
2.21
2.56
2.95
3.41
1042
1074
1112
1157
1208
1.99
2.28
2.62
3.02
3.48
1068
1101
1139
1184
1235
2.05
2.34
2.69
3.08
3.54
2077
2336
2596
2856
3115
4Hp STANDARD MOTOR & DRIVE
4Hp STANDARD MOTOR & HIGH STATIC DRIVE
5Hp OVERSIZED MOTOR & DRIVE
• Fan motor heat (kW) = 1.22 x Fan BkW
• Test condition :
①
Voltage : 415V
②
Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 165 l/s / 0.35 kW.