10. Performance data
Evaporator Fan Performance Data AK-H1208C02 (SI)
External Static Pressure(mm Aq.)
l/s
2.5
5.1
7.5
10.2
12.7
15.2
17.8
20.3
22.9
25.4
27.9
30.5
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW
External Static Pressure(mm Aq.)
l/s
33.0
35.6
38.1
40.6
43.2
45.7
48.3
50.8
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW
-
-
-
802
875
-
-
-
1.47
1.89
-
-
747
810
883
-
-
1.17
1.49
1.92
-
-
757
821
894
-
-
1.19
1.52
1.96
-
-
770
834
907
-
-
1.22
1.56
2.01
-
-
785
848
921
-
-
1.25
1.60
2.07
-
746
801
864
937
-
1.02
1.29
1.65
2.13
-
763
818
882
954
-
1.06
1.34
1.71
2.21
-
782
837
900
973
-
1.10
1.38
1.77
2.29
756
802
856
920
993
0.91
1.14
1.44
1.84
2.38
777
823
877
941
1014
0.95
1.19
1.50
1.91
2.47
799
845
900
963
1036
0.99
1.24
1.56
2.00
2.58
822
868
923
986
1059
1.04
1.29
1.63
2.09
2.70
1397
1572
1746
1921
2096
846
892
947
1010
1083
1.09
1.35
1.71
2.18
2.82
871
917
972
1035
1108
1.14
1.42
1.79
2.29
2.96
897
943
998
1061
1134
1.20
1.49
1.88
2.41
3.11
924
970
1024
1088
1161
1.26
1.57
1.98
2.53
3.28
951
997
1052
1116
1188
1.33
1.66
2.09
2.67
3.45
980
1026
1081
1144
1217
1.40
1.75
2.21
2.82
3.65
1009
1055
1110
1173
1246
1.48
1.85
2.34
2.99
3.86
1039
1085
1140
1204
-
1.57
1.96
2.47
3.16
-
1397
1572
1746
1921
2096
3Hp STANDARD MOTOR & DRIVE
5Hp OVERSIZED MOTOR & DRIVE
• Fan motor heat (KW) = 1.22 x Fan Bkw
• Test condition :
①
Voltage : 415V
②
Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 165 l/s / 0.35 KW.
• l/s of cooling capacity test : 1605 l/s at 10.16mmAq.
10.3 Fan Performance data