TECHNICAL SPECIFICATION
9
ENGLISH
TECHNICAL SPECIFICATION
Specification Sheet
Combination of AHU Communication Kit and ODU system with EEV Kit.
1) Maximum allowable capacity with HR Unit.
Compatibility of EEV Kits and IDUs.
1) Return Air is for PAHCMR000 / PAHCMC000
2) Supply Air is for PAHCMS000 / PAH PAHCMC000
3) IDUs includes Hydro Kit/DX ERV/FAU(OAU)
Model
PRLK048A0 PRLK096A0 PRLK396A0 PRLK594A0
Dimensions
Width
mm
217
217
349.5
409.5
Depth
mm
83
83
180
180
Height
mm
404
404
345.5
345.5
Net. Weight
kg
3.1
3.1
4.3
5.5
Casing
Color
Warm Gray
Material
Galvanized steel plate
Composition
Pipe Sensor
Liquid Pipe
Sensor Ø5, 5
kΩ
, 5m, Black
Gas Pipe
Sensor Ø7, 5
kΩ
, 5m, Red
Installation Manual
EA
1
1
1
1
EEV Controller (PAEEVA020)
EA
-
-
-
1
Rated Voltage
V
DC12 ±1.2
Connectable Outdoor Unit Capacity
HP
2 ~ 10
12 ~ 20
22 ~ 40
42 ~ 60
Liquid Pipe Size
mm
12.7
12.7
19.05
19.05
Operation Pressure
MPa
0 ~ 4.5
EEV Kit
AHU Communication Kit
Connection by ODU system
PAHCMR000
PAHCMS000
Heat pump
Heat recovery
PRLK048A0
O
O
O
O
PRLK096A0
O
O
O
O
PRLK396A0
O
O
O
X (Max 33.7 kW
1)
)
PRLK594A0
X
O
O (with PAHCMS000)
X
Case
Combination
Compatibility
Return Air
1)
Supply Air
2)
1
Multiple PRLK048A0 / PRLK096A0
O
O
2
Multiple PRLK048A0 / PRL IDUs
3)
O
X
3
PRL IDUs
X
X
PRL IDUs
X
X
4
PRL PRLK048A0 / PRLK096A0
X
X
PRL PRLK048A0 / PRLK096A0
X
X
5
PRL PRLK396A0 or PRLK594A0
(Exception : 2 x PRLK396A0)
X (O)
X (O)
PRL PRLK396A0 or PRLK594A0
X
X