![LG AHNW16809A3 Installation Manual Download Page 41](http://html.mh-extra.com/html/lg/ahnw16809a3/ahnw16809a3_installation-manual_213148041.webp)
Piping and Wiring for Outdoor Unit
Installation Manual
41
ENGLISH
The power cord
connected to the outdoor unit should be complied
withIEC 60245 or HD 22.4 S4 (This equipment shall be provided with a
cord set complying with the national regulation.
The connecting cable
connected to the outdoor unit should be
complied with IEC 60245 or HD 22.4 S4 (This equipment shall be
provided with a cord set complying with the national regulation.)
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
NORMAL CROSS-SECTIONAL AREA
CAUTION
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
When the connection line between the indoor unit and
outdooor unit is over 40m, connect the telecommunication
line and power line separately.
GN/
YL
1 Phase(Ø)
20m
m
3 Phase(Ø)
20mm
GN/
YL
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
W
ARNING:
Make sure that the screws of the terminal are free from looseness.
Round pressure terminal
Power wire
Model
Phase (Ø) Area (mm
2
)
AHUW056A3
1
4
AHUW076A3
AHUW096A3
AHUW126A3
6
AHUW146A3
AHUW166A3
AHUW128A3
3
2.5
AHUW148A3
AHUW168A3
Two kind of cables should be connected to the outdoor unit : One is ‘Power cable’, the other one is
‘Connecting cable’. Power cable is a cable which is used to supply external electricity to the outdoor unit.
This cable is generally connected between external power source (such as main electric power distribution
panel of user’s house) and the outdoor unit. Connecting cable is, on the other hand, used to connect
between the outdoor unit and the indoor unit to supply electric power to the indoor unit and to establish the
communication between the outdoor unit and the indoor unit.
Procedure for wiring to the outdoor unit is four steps. Before starting wiring, check if wire specification is
suitable and read following directions and cautions VERY carefully.
Electrical Wiring
1,MFL68681810,영영 2017. 7. 1. 영영 12:55 Page 41