Trouble Shooting Guide
01
Problem in Remote Room Air sensor
02
Problem in Refrigerant (Inlet side) sensor
06
Problem in Refrigerant (Outlet side) sensor
08
Problem in Water Tank sensor
13
Problem in Solar-thermal sensor
16
Problems in sensors
17
Problem in Water-inlet sensor
18
Problem in Water-outlet sensor
19
Problem in Water-interlim sensor
• Incorrect
connection
between
sensor and
PCB
• PCB fault
• Sensor fault
• Resistance: 10k ohm at 25 centigrade
(unplugged)
for Remote Room Air sensor
• Resistance: 5k ohm at 25 centigrade
(unplugged)
for all sensors EXCEPT Remote Room
Air sensor
• Voltage: 2.5Vdc at 25 centigrade
(plugged) (for all sensors)
• Refer resistance-temperature table to
check in different temperature
Code
No.
Description
Cause
Normal Condition
Ω
10k
Ω
Unplugged
Plugged
Check the resistance
Check the voltage
V
2.5Vdc
4. Trouble Shooting Guide
■
Error diagnosis and countermeasure flow chart
Is sensor properly
connected to PCB?
Is the resistance value
of sensor normal?
Connect properly to PCB
Change the sensor
Change the PCB
Yes
Yes
No
No