INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
More than
300
Fence or
obstacles
More than 700
More than 600
More than
300
Sunr
oof
Sunr
oof
Sunr
oof
Unit : mm
Capacity
(kBtu/h)
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant
(g / m)
Gas
Liquid
Standard
Max.
Standard
Max.
18
Ø 12.7 (1/2)
Ø 6.35 (1/4)
7.5
30
5
15
20
24(27)
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40
30
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40
36(38)
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40
48(53)
Ø 19.05 (3/4)
Ø 9.52 (3/8)
7.5
50
5
30
40
54(57/60)
Ø 19.05 (3/4)
Ø 9.52 (3/8)
7.5
50
5
30
40
If installed tube is shorter than 7.5 m, additional charging is not necessary.
Additional Refrigerant = (A -7.5) x Additional refrigerant (g)
Piping length and the elevation
INSTALLATION OF OUTDOOR UNIT
Installation Places
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.