INSTALLATION INSTRUCTION
ENGLISH
Installer Setting -E.S.P.
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
- If you set ESP incorrectly, the air conditioner may malfunction.
- This setting must be carried out by a certificated-technician.
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
- After entering into the installer setting
mode, select the E.S.P code value by
pressing the button.
* E.S.P code value : 03
1
Select the desired air flow rate with
the button. Whenever pressing
the button, [Lo
→
Med
→
Hi] will be
indicated.
2
Select the desired air flow rate value with
the temperature up(
▲
), down(
▼
) button.
* E.S.P value range : 0~255
- E.S.P value will be indicated at the upper
right section of the display window.
3
When pressing the button, currently
established E.S.P value will be set up.
4
When pressing the button and
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be
released.
- If there isn’t any button input for more
than 25 seconds, the installer setting
mode will also be released.
5
OPER
MODE
OPER
MODE
FAN
SPEED
FAN
SPEED
OPER
MODE
- Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
- E.S.P value can be varied according to the products.
- In the case of going to the next air flow rate stage by pressing the fan-speed button during the
setup of the E.S.P value, the E.S.P value of previous air flow rate will be maintained by
remembering the E.S.P value prior to the shift.