Refrigeration Cycle Diagram
- 14 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Heat Pump
ORIFICE
(Capillary only
for 60k Btu)
ORIFICE
(Only for
60k Btu)
HP
• If 60K Model is installed at a distance of 15m, 525g of refrigerant should be added
(15-7.5) x 70g = 525g
30k Btu/h
5/8"
3/8"
7.5
30
5
15
70
36k Btu/h
5/8"
3/8"
7.5
30
5
15
50
42k Btu/h
3/4''
3/8"
7.5
30
5
15
70
48k Btu/h
3/4''
3/8"
7.5
30
5
15
70
60k Btu/h
3/4''
3/8"
7.5
30
5
15
70
72k Btu/h
1''
1/2"
7.5
25
5
20
70
90k Btu/h
9/8''
5/8"
7.5
30
5
20
90
100k Btu/h
9/8''
5/8"
7.5
30
5
20
100
Capacity
Gas
Liquid
Elevation B(m)
Piping Length
A(m)
* Additional
Refrigerant
(g/m)
Pipe Size (Diam-
eter: Ø)
inch
Standard
Standard
Max.
Max.
Model Name
Orifice Number
LBNS3061BL/LBNS3062BL/LBNS3063BL/LBNS3064BL
63
LBNK3661BL
62
LBNK3663BL
TBA
LBNK4261BL
74
LBNK4262BL/LBNK4263BL
72
LBNK4881BL
86
LBNK4882BL/LBNK4883BL
90
LBNM7280BL/LBNM7281BL
98
LBNM9080BL/LBNM9081BL
84
LBNM1080BL/LBNM1081BL
104
Orifice Number