INSTALLATION INSTRUCTION
ENGLISH
25
Model
Step
CMM
Static Pressure[mmAq(Pa)]
2(20)
2.5(25)
3(29)
4(39)
6(59)
8(78)
10(98)
Setting Value
ABNW24GM1T0
ABNQ24GM1T0
HIGH
18
94
96
101
106
109
115
121
MID
16.5
89
91
96
101
105
111
117
LOW
14
79
81
87
93
99
105
112
Model
Step
CMM
Static Pressure[mmAq(Pa)]
2(20)
2.5(25)
3(29)
4(39)
6(59)
8(78)
10(98)
Setting Value
ABNW18GM1T0
ABNQ18GM1T0
HIGH
16.5
85
86
88
92
99
106
115
MID
14.5
75
77
85
88
93
102
111
LOW
13
71
73
76
85
89
98
107
NOTE
!
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
Model
Factory set (E.S.P.)
mmAq(Pa)
Lower Limit (E.S.P)
mmAq(Pa)
Upper Limit (E.S.P)
mmAq(Pa)
ABNW60GM3T0
ABNQ60GM3T0
ABNW60LM3T0
ABNQ60LM3T0
6(59)
2.5(25)
14(137)
ABNW48GM3T0
ABNQ48GM3T0
ABNW48LM3T0
ABNQ48LM3T0
6(59)
4(39)
12(118)
ABNW42GM3T0
ABNQ42GM3T0
6(59)
4(39)
12(118)
ABNW36GM3T0
ABNQ36GM3T0
8(78)
2(20)
10(98)
ABNW30GM2T0
ABNQ30GM2T0
8(78)
2(20)
10(98)
ABNW24GM1T0
ABNQ24GM1T0
8(78)
2(20)
10(98)
ABNW18GM1T0
ABNQ18GM1T0
8(78)
2(20)
10(98)