- 2 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Specification
Nominal Capacity
Cooling
kW
(Min~Rated~Max) Btu/h
Heating kW
Btu/h
Nominal Input
Cooling
kW
(Min~Rated~Max) Heating
kW
Energy label
Testing Combination
Running Current
Cooling
A
Heating A
Starting Current
(Cooling/Heating)
A
Power Supply
Ø / V / Hz
Power Supply Cable (outdoor)
No.x mm
2
Power and transmission cable (outdoor to BD)
No.x mm
2
Power and transmission cable (BD to indoor)
No.x mm
2
Dimensions W*H*D
mm(inch)
Net Weight
kg(lbs)
Max. Number of Connectable Indoor Units
Compressor (Inverter)
Type
Qty x Model
Motor Type
Oil Charge volume
cc
Oil Type
Refrigerant
Charge (at 5m)
g(oz)
Type
Control
Heat Exchanger
Rows x Column x FPI
Defrosting Method
Fan Capacitor
µF/Vac
Drive
Discharge direction
Side / Top
Air Flow Rate
CMM(CFM)
Noise Level(H/L)
Sound Pressure at 1m
dB(A)±3
Piping connections
Liquid(Ø)
mm(inch)
Gas(Ø) mm(inch)
Max. Interunit Piping Length Total Piping(Main+Total Branch)
m
Main Piping
m
Total Branch Piping
m
Each Branch Piping
m
Max. Elevation Difference
Indoor Unit~Outdoor Unit
m
Indoor Unit~Indoor Unit
m
Outdoor Unit
A9UW566FA3[FM56AH U33]
4.0~16.7~18.52
13,800~57,000~63,200
4.5~17.87~18.75
15,456~61,000~64,000
1.0~4.96~5.65
1.25~4.62~5.70
A/A
MS09AH N40*8EA
4.6~21.7~24
7.4~22.4~26
-
1/220~240/50
3*4.0
4*1.25(Including Earth)
4*0.75(Including Earth)
950*1380*330 (37.4*54.3*12.3)
108(238.1)
9
Twin-Rotary
5JD420Z
BLDC
1300
FV50S
4800(169.3)
R410A
EEV
2R x 64C x 17
Reversing cycle
-
DC
Side
60(2,119) x 2
59
9.52(3/8)
19.05(3/4)
145
55
90
15
30
15
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Conversion Formula
kW = Btu/h x 0.0002931
cfm = CMM x 35.3