- 24 -
Intake Air temp.
Setting temp.+3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
INDOOR FAN
Low
OFF Low
Low
OFF
■
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot Start
Low
Selecting
Fan Speed
minimum 3min
Selecting fan
speed
minimum
10sec.
1min
A
A
minimum
1min.
minimum
10sec.
B
■
Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
PIPING
TEMPERATURE
1min
COMPRESSOR
INDOOR FAN
OFF
LOW
Selected Fan
ON
22
°
C
25
°
C
• A point;
While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed, when
it becomes lower than 40˚C fan stops.
• B point;
When the indoor Heat-Exchanger temperature is higher than 31°C, fan operates at selected fan
speed, when it becomes lower than 31°C, the fan operates at low speed for 10sec, after 10sec, it
operates at selected fan speed.
Summary of Contents for A2UN186FA0
Page 104: ... 104 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Page 105: ... 105 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Page 106: ... 106 3 Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Page 107: ... 107 4 Convertible Type Indoor Unit ...
Page 109: ... 109 6 SUB P W B ASSEMBLY Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Page 110: ... 110 7 Outdoor Unit MAIN P C B ASM V P U N W ...
Page 111: ... 111 Schematic Diagram 1 Room Type Indoor Unit ...
Page 113: ... 113 3 Art Cool Type Indoor Unit ...
Page 114: ... 114 4 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Page 132: ...P No 3828A20097N August 2003 Printed in Korea ...