72 Multi type Air Conditioner
Troubleshooting Guide
Error Code
■
Trouble Shooting
Error
Title
Cause of error
Check point & Normal condition
code
01
Indoor air sensor
02
Indoor inlet pipe sensor
06
Indoor outlet pipe sensor
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 10K
Ω
/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
Normal resistor : 5K
Ω
/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
Normal resistor : 5K
Ω
/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
Ω
10K
Ω
2.5Vdc
Check the resistance / voltage
V
❑
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor
3. If the resistance of the sensor is 10K
Ω
/5K
Ω
at 25°C, then sensor is normal
4. If the resistance of the sensor is 0 K
Ω
or
∞
, then sensor is abnormal.
➔
Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc / at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal.
➔
Repair or Change the PCB
Summary of Contents for A2UC243FA0 (LMU240CE)
Page 56: ...56 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit ...
Page 57: ...Service Manual 57 Schematic Diagram ...
Page 60: ...60 Multi type Air Conditioner Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Page 62: ...62 Multi type Air Conditioner Schematic Diagram 3 Outdoor Unit 1 Component side ...
Page 63: ...Service Manual 63 Schematic Diagram 2 Solder side ...