Abnormal Door status sensing
1. In case of the operation of the Door status is reversed :
: Check the wire connection and the setting of LCM is proper setting NC/NO
2. The door status is no changed :
1) Confirm the wire connection and the setting of LCM
2) Check the door-lock have sensor can check door status.
3) Even though above conditions have no problems, LOCK should be changed
3. Status change in more frequent
1) Check the wire connection
2) Change the Door-lock
3. EM / Deadbolt / Strike
One-direction check-point