background image

Power supply 

150-240V AC

Pump connection

(Max 4A/220V)

Pt1000 Sensor 
Storage Tank

Pt1000 Sensor 
Collector

Connections

Levtech Service 

& Prodtuction SRL

Lueta Nr. 319, Romania

+40758576007

offi[email protected]

www.levtech.ro

Summary of Contents for LSP-SC1

Page 1: ...Lueta Nr 319 Romania 40758576007 of ce levtech ro www levtech ro SOLAR CONTROL LSP SC1 MANUAL Levtech Service Prodtuction SRL...

Page 2: ...hich consists of a solar collector storage tank and a pump Comparing the temperatures of the collector and of the storage tank this device controls the pump and makes sure that the entire system is sa...

Page 3: ...ing off 0 20 Sec Potentiometer adjusts the starting temperature of controlling 0 40 C Jumper determins whether the system is lled with antifreeze liquid 500mA safety fuse on the power supply Alarm res...

Page 4: ...can be set from 0 to 22 C The Start_Temp potentiometer sets the starting temperature for controlling the system The temperature of the collector has to be higher then the given starting temperature i...

Page 5: ...reaches 20 C it will start the pump and will run it until the temperature of the collector reaches 15 C When the antifreeze mode is off the pump will start at 5 C and will switch off at 0 C to avoid t...

Page 6: ...n the collector reaches the 115 C The pump will be stopped to avoid damage in the pipe line caused by the hot water The sound alarm can be switched off with the button and the pump can be controlled m...

Page 7: ...2 cools down to 55 C 50 10 2 Normal mode Holiday mode The system automatically cools down during night time to avoid damage caused by overheating the system Winter mode The controller doesn t let the...

Page 8: ...37mm 150 mm 155 mm Dimensions Levtech Service Prodtuction SRL Lueta Nr 319 Romania 40758576007 of ce levtech ro www levtech ro...

Page 9: ...supply 150 240V AC Pump connection Max 4A 220V Pt1000 Sensor Storage Tank Pt1000 Sensor Collector Connections Levtech Service Prodtuction SRL Lueta Nr 319 Romania 40758576007 of ce levtech ro www levt...

Page 10: ...e controller 20 C to 60 C Dimensions W x H x D 155 x 150 x 37 mm Weight 65g Display 3digit 7 segment display Maximum load of the pump 4A Sensor inputs Pt1000 Measuring range 50 C to 180 C Temperature...

Page 11: ...tomatic off 105 C in collector Antifreeze mode Pump starts at 20 C degrees Pump switches off at 15 C degrees None antifreeze mode Pump starts at 5 C degrees Pump switches off at 0 C degrees Pump delay...

Page 12: ...ff during storms Electrical and electronic appliances often contain materials which if handled or disposed of incorrectly could be potentially hazardous to human health and to the environment They are...

Page 13: ...by plugging in the collector 5 Done 6 T1 T1 T2 T1 SOLAR CONTROL Power ON Heat pump ON Error LSP SC1 INSTALLATION INSTRUCTIONS Remove the front cover of the controller and mount the enclosure on the wa...

Page 14: ...settings Using a screwdriver set the delay time of the pump switch off by turning the potentiometer on the left Using a screwdriver set the temperature difference by turning the potentiometer in the m...

Reviews: