Daylight Harvesting Made Simple.

This user’s guide applies to the following part numbers:

Network Remote, Dimmed, Two Room, 120V or 277V

Network Remote, Dimmed, Two Room, 347V

Network Remote, Dimmed Version, 2 Zone, 2 Relay, 
120V or 277V

Network Remote, Dimmed Version, 3 Zone, 1 Relay, 
120V or 277V

Description

2

3

2

2

0-10V 

Outputs

2

1

2

2

Relay 

Outputs

m Z n 2 2 - 1 0 2

m Z n 3 0 - 1 0 1

m Z n 2 0 - 1 0 2

m Z n 2 2 - C 0 2

Model 

Number

Features between models vary. As such, not all information in this manual 

applies to all models.

Network Remote, Dimmed Version, 3 Zone, 1 Relay, 
347V

Network Remote, Dimmed Version, 2 Zone, 2 Relay, 
347V

2

3

2

1

m Z n 2 0 - C 0 2

m Z n 3 0 - C 0 1

REMOTE NETWORKING ADDENDUM

Revision A 5/2007

Summary of Contents for miniZ mZn20-102

Page 1: ...work Remote Dimmed Version 3 Zone 1 Relay 120V or 277V Description 2 3 2 2 0 10V Outputs 2 1 2 2 Relay Outputs mZn22 102 mZn30 101 mZn20 102 mZn22 C02 Model Number Features between models vary As such not all information in this manual applies to all models Network Remote Dimmed Version 3 Zone 1 Relay 347V Network Remote Dimmed Version 2 Zone 2 Relay 347V 2 3 2 1 mZn20 C02 mZn30 C01 REMOTE NETWORK...

Page 2: ...NOTES ...

Page 3: ...e 1 DESCRIPTION OF APPLICATION 2 CABLE WIRING JUMPERS 4 CONFIGURATION DIP SWITCH SETTINGS NETWORK 5 NOTES Z MAX CONFIGURATION 6 NOTES MINIZ OPERATION 7 TABLE OF CONTENTS STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 ...

Page 4: ...he Z MAX Relay Panel can control all scheduled events of the miniZ Remote Network controller In addition it can be configured to operate with the wall station controls and or occupancy sensors either directly connected to the Z MAX Master or to the miniZ Remote In all cases the photocell needs to be connected directly to the miniZ Remote Communications are handled over a LumaNET bus cabling with C...

Page 5: ...The following is an example of a one line diagram for a typical application This illustrates how the Remote Networking miniZ is used with a Z MAX Master Relay Panel Page 3 ...

Page 6: ...ld be open on one pin only JP4 Shield should be open on one pin only JP3 ROUTES POWER If both jumpers are open on one pin only no power connections are present If a jumper is on the center two pins the two cables are connected and the miniZ is not If a jumper is on the left two pins the miniZ sends power to the left cable If a jumper is on the right tow pins the miniZ sends power to the right cabl...

Page 7: ...e for networking F see miniZ operation on page 7 1 32 Add to get slave address 1st relay number is Address x 4 3 3 zone units have only the 1st relay 2 channel 2 rooom have 1st 2nd relays ON 1 2 3 4 5 6 7 8 9 10 1 2 4 8 16 32 F Z Address 12 Relay 45 48 STEP 3 ...

Page 8: ...tch example a miniZ is at Address 12 The 1st relay discrete is 45 The 1st only switchbox is at the same address as the 1st relay Except in 3 zone units the 2nd switchbox and the 2nd relay use the second relay discrete number In 1 room units the Occupancy Sensor is the 3rd discrete and the Photocell Sensor is the 4th discrete In 2 room units the 1st Occupancy Sensor is at the 3rd discrete and the 2...

Page 9: ... Z MAX master and not processed by the miniZ If DIP switch F 7 is off the miniZ will process the switchbox and occupancy events including Dim Bright and Max from 5 button stations These events are also sent to the Z MAX master Note The miniZ always uses the Photocell so daylighting wil operate normally in either setting STEP 5 ...

Page 10: ...Leviton Lighting Management Systems Division Headquarters 20497 SW Teton Tualatin Oregon 97062 Customer Service 800 736 6682 Facsimile 503 404 5600 Technical Support 800 959 6004 P N PK 93453 10 00 0A ...