i Series i24, i24e, & quad Installation Supplement 

 

Page 1 of 3 

LIT-30955-02 
 

 

Wall Mounted Dimmer Racks 

Installation and Maintenance Manual Supplement 

Applies to 

i

24, 

i

24e and 

i

48 Quad 

 

Enclosed is a copy of the Installation and Maintenance Manual for the original product.  The 
wall- mounted units are very similar to the floor-supported units except in the way they mount 
and the size of the feeder lugs.  The Quad version also includes additional load lugs.  This 
supplement serves as a modifier to that manual for the wall- mounted product.  Please follow the 
instructions in the manual except where modified below. 
 
Page 2, Chapter 3 – The wall- mounted units are separate stand-alone dimmer racks.  They may 
be mounted side-by-side but are not fastened together.  Disregard this chapter. 
 
Page 7, Chapter 4 – The wall- mounted units are provided with concentric knock-outs top and 
bottom in lieu of un-punched conduit entry panels.  Two 1.5 / 2 / 2.5” T.S. and Eight 0.5 / 0.75 / 
1 / 1.25” T.S.  knock-outs are provided in both locations. 
 
Page 10, Chapter 5 – Also allow 1” clearance on the left side so that the door can fully open. 
 
Page 10, Chapter 6 – The wall- mounted units are attached to the wall via four holes in the back 
to accept 5/16” bolts.  The rack must be mounted in a substantial manner to support its 179 lbs. 
plus the weight of any field wiring and conduit.  The use of Unistrut or similar steel channel is 
recommended. 
 
Page 11, Chapter 9 – The 

i

24 and 

i

24e are provided with single feeder lugs with the option for a 

second set.  The 

i

48 Quad is provided with dual feeder lugs. 

 
Page 12, Table 1 – Line Lugs (rated for 90

o

C copper only at 75

o

C ampacity) 

 

 

 

6 AWG – 250 kcmil.  375 in- lbs. 

 

 

       Ground Lug 

 

 

 

14-10 AWG   

35 in- lbs. 

 

 

 

8 AWG 

 

40 in- lbs. 

 

 

 

6-4 AWG 

 

45 in- lbs. 

 

 

 

2-1/0 AWG 

 

50 in- lbs. 

 