GreenMax
TM
DRC 2 Port Analog Interface
Cat. No. DRID0-C02, DRID0-CB2
INSTALLATION INSTRUCTIONS
ENGLISH
WARNINGS
•
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST
THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
CAUTIONS
• Use this device with
copper or copper clad wire only.
• For indoor applications only.
• Save these instructions.
The GreenMax DRC Low Voltage Analog Interface (AI) is designed to accept input from low voltage sources
like occupancy sensors, switches, photocells, and other related systems, and to interface to other external
systems via low voltage input.
Mount with one of the following methods:
Install into a 4-11/16 in. electrical junction box.
NOTE:
Electrical junction box must have a depth of 2 in. or greater.
Introduction
DRID0-C02 Installation Options
DRID0-CB2 Installation
Interface
WARNING: TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWER
at circuit breaker or fuse and test that power is off before wiring
Before Installation
DIN rail
DIN Rail Mounting
Consider the items noted below:
• When surface mounting using the mounting ears, ensure environment is free from debris and wiring is protected.
• For jurisdictions where all Class 2 wiring must be in conduit or if the device must be in a metal enclosure,
surface mounting is not appropriate.
• For compliance with Chicago plenum requirements, installation in metal box is required.
b.
c.
PK-A3289-10-00-5A
Surface Mounting
a.
a.
a.
Feed wires through knockouts and wire device.
Set unique LumaCAN network address.
(refer to the
Wiring and Network Details
section).
b.
Mount plate to junction box.
1.
DC COM
= COM
2. AI1
&
AI2
= Analog Input
• 0.5-24VDC at 10 bit resolution for analog inputs.
• 0.5-10VDC for use with a photocell.
•
+24V/Open for external contact closure as you would use with a switch or a photocell contact closure. May be
used with a momentary or maintained device.
3.
+V OUT
= Output voltage to devices. Actual voltage will be same as input passthrough from LumaCAN. Output is
short circuit protected.
4.
STATUS LED
= Shows network status. The LEDs have the following functions:
•
AI1 = Solid Yellow when Analog Input #1 is Active (> 0.5V)
•
AI2 = Solid Yellow when Analog Input #2 is Active (> 0.5V)
•
AI1/AI2 = Blink rapidly when in bootloader mode.
•
RX/TX = Solid Green when network connected. Blinks Green on network traffic.
5.
LumaCAN
= LumaCAN Network connections
6.
TERM
= Provides Network termination. Jumper to be installed if last device on network. Remove jumper if not an
end device.
7.
ADDR
= Used to set LumaCAN network address.