FEBC Operation
Page 6
E. Connect a voltmeter between the AN2 terminal and any RET terminal on connector P4. Adjust Potentiometer
R20 for the desired full-scale output voltage.
F. Connect a voltmeter between the AN3 terminal and any RET terminal on connector P4. Adjust Potentiometer
R21 for the desired full-scale output voltage.
G. Connect a voltmeter between the AN4 terminal and any RET terminal on connector P4. Adjust Potentiometer
R22 for the desired full-scale output voltage.
H. Reset the option dipswitch from the CALIBRATE function. Set switch #7 on S4 to the 'off' position.
I.
Cycle power off and on again to remove FEBC from calibrate mode. All analog outputs will reflect incoming
signals or be set to zero levels.