2 INSTALLATION CHECKLIST

2.1   Configuration Software Required

The A8332 (Flex I/O Module) requires configuration before it may be used. This guide will cover two primary 
ways to achieve this. (Consult A8332 manual for third party software or hardware integration.)

2.1.1   

Obvius Configuration Console: 

The Obvius Configuration Console (OCC) is a software application 

designed to assist in the setup and commissioning of Obvius hardware products. The OCC software is 
available for free download at http://www.obvius.com/Products/Configuration_Console.

2.1.2  Energy Monitoring Hub users may use the integrated web browser interface to set up and  

configure the A8332 (Flex I/O).

4

2.2 Modbus Address

Before the Flex I/O can be used, select a Modbus address for the 
Flex I/O. This address must be unique among all Modbus devices 
in the system. The A8332 supports address 1 through 127.

Select an address, and set the DIP switches to match.

The sum of the value of the switches is the address. In the 
example to the right, address 52 is set by placing switch 4, 16 and 
32 to the on position.

Note: 4 + 16 + 32 = 52

3.1 Installation

3.1.1  Connect the power supply to the input terminals on the  

A8332 module.

3.1.2  Attach the RS485 +, - and shield wires to the A8332 module. 

Attach the other end of the RS485 line to the Modbus master 
device, such as an EMB Hub. Be careful to observe polarity 
on both ends of the RS485 connection. RS485 wiring runs 
should be limited to 4000 ft.

Modbus

Address

19200/9600

on

64

32

16

8

4

2

1

WEB 

VERSION