21
04: Frequency range for bypass
Interface
Setting
Parameter 2:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3:
Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: ECO mode enable/disable
Interface
Setting
Parameter 3:
Enable or disable ECO function. You may choose
following two options:
DIS:
disable ECO function
ENA:
enable ECO function
If ECO function is disabled, voltage range and frequency range for
ECO mode still can be set, but it is meaningless unless the ECO
function is enabled.
06: Voltage range for ECO mode
Interface
Setting
Parameter 2:
Low voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
Parameter 3:
High voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
07: Frequency range for ECO mode
Interface
Setting
Parameter 2:
Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3:
Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.