Technical data and ordering data
Leuze electronic
MSI 100/200
101
14 Technical data and ordering data
14.1
Technical data MSI 100 and
MSI 200
Logic / supply A1/A2
Rated control circuit supply voltage U
S
Permissible range
24 V DC (A1/A2)
18 V DC … 30 V DC
(incl. all tolerances, incl. residual ripple)
Rated control supply current I
S
Typ. 110 mA
Limiting continuous current
Max. 6 A
(for looped-through current paths A1/A1 and A2/A2, see "Double terminal con-
tacts A1/A1 and A2/A2" on page 35)
Filter time
Typ. 20 ms (load-dependent, on voltage dips for U
S
)
Status indicator
3 x green LEDs
1 x red LED
Protective circuit
Yes, within the scope of the operating voltage limits
Safe digital inputs I0 to I19
Quantity
10 (two-channel, up to SIL 3)
20 (one-channel, up to SIL 2)
Type
digital, type HTL
Input voltage range "0" signal
0 V DC … 5 V DC (for safe off)
Input voltage range "1" signal
11 V DC … 30 V DC
Typical current consumption at U
S
4 mA
Maximum total cable length
2000 m
Status indicator
20 x green LEDs (1 LED per input)
Safe digital outputs O0 to O3 and ground-switching outputs O0- and O1-
Quantity (type)
4 (safe semiconductor outputs, up to Cat. 4 in accordance with EN ISO 13849-1)
2 (ground-switching outputs)
Nominal voltage
Permissible range
24 V DC (supply via 24V/0V)
18 V DC … 30 V DC
(incl. all tolerances, incl. residual ripple)
WARNING: Loss of the safety function
The use of unsuitable voltage supplies and the incorrect connection of the voltage supply can result in the loss
of the safety function.
•
Only use power supply units with safe insulation and SELV/PELV in accordance with EN 50178 /
VDE 0160.
•
Connect the output-side GND connection of the power supply unit to the functional earth (FE) of the system.