background image

6.0 

Fault messages, possible malfunctions, corrections

 

6.1 

Fault messages on the display

 

Message on Display  Possible cause 

Correction 

Thermal Fault 1 

The controller contact of the 
according pump initiates.  

If the pump in use does not come with the required thermal 
motor protection contact the mode needs to be deactivated in 
the menu (compare to 5.2.7.Thermal Fault 1, Thermal fault 2). 
Check the pump. If it is plugged, clean out the foreign matter. 
Check the motor for sufficient cooling (dry run). 

Thermal fault 2 

The limiting contact of the 
according pump initiates.  

If the pump in use does not have the required thermal motor 
protection contact every pump that is used needs to be bridged. 
(compare to 7.3.3 Thermal motor protection contact). 
Check the pump. If it is plugged, clean out the foreign matter. 
Check the motor for sufficient cooling (dry run). 
After the pump has cooled off, push the button “Quittung” in 
order to unlock the pump.  

Pump off 

Phase 2 is missing or the control 
unit is being operated without 
charge.  

Check feed-in, pump cables, and pump 

High-water-Alarm 

The level has exceeded the 
flood setting  

Check pump for mode or high-water level 

High-water switch 

Contact for the high-water 
switch has closed  

Check if pump/ floating switch are functioning 

Reverse signals 

start/stop level 

The settings for start and stop 
levels interfere.  

Check level settings 

Reverse signals 

start/flood level 

The settings for high-water 
alarm and start level interfere 

Check settings for level 

Runtime error 

Pumps run without interruption 
for longer than the time set. 

Check function of pump 

Floating switch 
malfunction 

Validation of floating switches, 
wrong order  

Check if floating switch is functioning and check if it is 
connected to power correctly  

Dry run protection 

activated 

Contact for dry run protection 
has been activated  

Check functioning of pump / floating switch 

Interface < 3 mA 

Signal of external level sensor 
lower than 3 mA 

Check level sensor, Ex-barrier, and electrical connections 

Please check control 
settings 

The effective range of the 
external level sensor has been 
changed. The level settings lie 
outside the effective range.  

Check settings for level 

Rotating field 

One or two phases are missing, 
or rather the rotating field is not 
correct 

Check if all 3 phases are adjacent and if the rotating field is 
correct.  

ATEX: level less than 

stop level 

The ATEX mode has been 
activated and the level lies 
below the stop level of the 
chosen pump.  

Before being able to activate the pumps, the level in the Ex-area 
needs to rise over the stop level of the pump.  
As long as the pumps are not in the Ex-area, the ATEX mode can 
be deactivated in the menu.  

PS

MEGA 

1

www.lesa.de

         

9

 

Summary of Contents for PSMEGA 1

Page 1: ...e pump control Options FS PSMEGA1Freiluftsäule Messglocke V4A Schwimmschalter Tauchsensor Operating Manual www lesa de PSMEGA1_2v0 04092020 LESA Messtechnik Hegholt 59 22179 Hamburg Germany Phone 49 40 641 00 41 Fax 49 40 641 18 36 ...

Page 2: ...n menu images and notes on configuring the parameters 5 1 Table of possible settings 5 2 Supplements to the individual items in the configuration menu 6 0 Error reports in the display potential errors assistance 6 1 Table of possible fault messages 6 2 The settings in the menu cannot be changed 6 3 Motor contactor monitoring 7 0 Installation pneumatic and electrical connection and connection of 3 ...

Page 3: ...and maintenance of the switchgear must hold the requisite qualifications 2 3 Safety instructions for the operator Observe the existing regulations governing accident prevention the VDE specifications and stipulations of the local energy supply company When opening the device removal of the panel or terminal cover or working on the pumps the control must be switched off from the power supply throug...

Page 4: ...rnal audible alarm Collective fault alarm fixed voltage and potential free High water alarm potential free Memory number of pump starts Operating hours counter Ammeter Pump change Forced switchover High interference immunity Easy to operate ATEX mode Service mode Input for float switch dry run protection Analogue outputs 0 10 V and 4 20 mA Fault memory stores the last 4 faults Automatic display il...

Page 5: ... The green LED will blink If the pump is being run via the manual function then it will automatically shut off after 2 minutes and the green LED will flash irregularly The automatic and manual operation are shut down using this button The green LED is off The pump is switched based on the level The green LED is lit continuously If power is interrupted during manual mode then the control system wil...

Page 6: ...arm Is deactivated Is activated Is activated The fault information relay will be synchronized Instead of a flashing light it is possible to use a more economic steady burning light Thermal fault 1 Is deactivated Is activated Is deactivated There is no bimetallic contact alarm contact connected to terminal 12 13 Rot field fault Is deactivated Is activated Is activated in case the phase sequence is ...

Page 7: ... the menu 5 2 8 Error memory Last fault The last 4 errors that occurred remain stored in non volatile memory and can be retrieved in the menu under Last fault Caution Last fault 1 is the last fault that occurred If Last fault 1 is called up in the menu the last errors can be deleted from the memory with the acknowledge button 5 2 9 Rotary field error The rotary field monitoring monitors both the p...

Page 8: ...y language can also be changed when service mode is deactivated 5 2 17 Menu items data import and export The PSMEGA 1 offers the option of writing and reading configuration files 5 2 18 FatFS Filename At this point the file name is assigned for the configuration and log files The file name PSMEGA 1 is preset A code page can be opened by pressing the select acknowledge button A character can be sel...

Page 9: ... switch are functioning Reverse signals start stop level The settings for start and stop levels interfere Check level settings Reverse signals start flood level The settings for high water alarm and start level interfere Check settings for level Runtime error Pumps run without interruption for longer than the time set Check function of pump Floating switch malfunction Validation of floating switch...

Page 10: ...n must be paid that a right rotary field is created The terminals are labelled L1 L2 L3 N The PE terminals are implemented as a brass rail 7 3 1 Connection of the pump The connections L1 L2 L3 of the pump are directly attached to the motor contactor The protective earth conductor is connected to the remaining PE terminal The bimetallic contact which unlocks the pump after it has cooled down needs ...

Page 11: ...prox 24 volt In the delivered state the measuring range of the level sensor is set in such a manner that it matches the measuring range of the internal pressure sensor In the event that the level sensor should be connected with a different measuring range then the corresponding setting must be changed in the menu see section 5 2 14 The output is active i e the sensor is supplied with voltage by th...

Page 12: ...e 20 bis 50 C Dimensions 250 x 225 x 115 mm HxWxD Dimensions with cable gland and air connection Fuse 5 x 20 1AT alarm output Voltage supply for 4 20 mA sensor and float switch 24V DC Cable glands 2 x M25 x 1 5 1 x M16 x 1 5 3 x M16 x 1 5 blind plug Hose attachment 6 8 mm Other hose connections are available on request Software version Ver 0 3 When opening the device removal of the panel or termin...

Page 13: ...12 0 Annex Terminal block wiring diagrams Terminal connection of 3 motors Terminal connection of 1 motors Caution When connecting 1 motors the maximum connected load is 2 4 KW PSMEGA 1 www lesa de 13 ...

Page 14: ...Relay outputs signal inputs and analogue outputs PSMEGA 1 www lesa de 14 ...

Page 15: ...A 180 mm B 180mm o 5 0mm PSMEGA 1 www lesa de 15 ...

Page 16: ...le Alarmmodule GSM Module Messumformer Fernwirk Pumpsysteme Messglocken Pneumatische Leitung Schaltanlagenbau Automatisierung Fernwirktechnik Freiluftsäulen komplett bestückt mit PS1 LCD PS2 LCD Kompaktschaltschrank LCD2 System Metall GfK Außenschränke Leersäulen EVU Anschlusssäule Verschraubungen für pneumatische Leitung Schwimmschalter Tauchsensoren Ultraschallsensoren Stabsonden Druckschalter A...

Reviews: