8.0
Test mode without pump
8.1
In order to test the control unit without pumps
the following needs to be considered
- It is sufficient to connect N1 and L1
- Unless the motor current protection is set to 0 A, the
message “
L pump off”
will appear
- Terminals 13 / 14 need to be bridged, otherwise the
message
“Thermal Fault 2”
will appear.
- Thermal fault 1 need to be deactivated in the settings
menu, otherwise the message
“Thermal Fault 1”
will
appear.
9.0
Technical data
Operating voltage:
3 ~ 400V (L1, L2, L3, N, PE)
Frequency
50 / 60 Hz
Control voltage:
230V / AC
Power consumption:
(Contactor activated)
< 7,5 W
Power consumption in idle state
< 5 W
Max. installed power
P
2
< 5,5 KW
Range of the electrical motor current
monitoring
0,3 – 16 A
(Here, the limit values featured in the table under point 1.1 of the
safety instructions must be adhered to)
Alarm contact 230 V
1 A
Alarm contact potential-free
3 A
Housing:
ABS
Protection class:
IP 54
Pressure range (internal sensor):
0 - 1 mWs (0 - 2mWs Option)
Transport and storage temperature - 30° bis + 60°C
Operating temperature range:
- 20° bis + 50 °C
Dimensions:
250 x 225 x 115
mm (HxWxD)
Dimensions with cable gland and air connection
Fuse:
5 x 20 1AT (alarm output)
Voltage supply for
4-20 mA sensor
and float switch
24V / DC
Cable glands:
2 x M25 x 1,5
1 x M16 x 1,5
3 x M16 x 1,5 blind plug
Hose attachment:
6/8 mm
(Other hose connections are available on request.)
Software version:
Ver. 0.3
When opening the device (removal of the panel or terminal cover)
or working on the pumps, the control must be switched off from the
power supply through the fuse or a separate main switch.
Technical specifications subject to modification!
10.0 Norms:
Applicable EC directives:
EC Low Voltage Directive 2014/35/EC
EC Electromagnetic Compatibility Directive 2014/30/EC
Applied harmonised standards, in particular:
EN 60204 - 1: 2014
EN 60730 - 1: 2016
IEC 61000 - 6 - 3: 2006
IEC 61000 - 6 - 2: 2016
11.0 Annex:
Status LED – GSM module:
Flashing constantly =
The board is in the initialisation phase
Illuminated constantly
=
The board has initialised and has
connected with the provider
Flashes once briefly,
then extended pause
=
The modem is not responding
Flashes twice briefly,
then extended pause
=
The SIM card has not been found
Flashes three times briefly
=
The GSM signal strength is too weak
PS
MEGA
1
www.lesa.de
12