background image

3.0

 

Configuration, control elements and function displays

 

3.1     

  All values and settings can be queried using the digital potentiometer display. If a until is going to be changed, 

adjust the control unit until the corresponding setting appears on the display. Now press the select / cancel 
button. The value last saved will start to blink. The digital potentiometer display can now be used to change 
the setting. Quick turns will change the values more rapidly, while slow turns make it possible to make more 
precise changes. Once the desired value has been reached, use the select / cancel button to confirm. The 
value will stop blinking and be stored. Check all values prior to commissioning.  
The display will automatically return to the default setting after 20 seconds. 

CAUTION!

 

Operating hours and pump starts are counted continuously, 
it is not possible to adjust or reset them. 

3.2

 

 Control elements 

- Display

Pressing the digital potentiometer will query all settings, and moving the display knob will 
query all error reports, operating hours, number of pump starts and motor current. 
Moreover, settings are made using the digital potentiometer. If the knob is not moved for more 
than 20 seconds, then the display will jump back to the default setting. (see above, 
Configuration chapter) 

- Selection/cancel

Button

Pressing this button will confirm the errors over-current, P1 - P2 without load and will confirm 

thermal error 2 after remediating the cause. Should an error continue, then only the common 
error report relay and the piezo buzzer will be shut off. This also applies for thermal error 1 
and the high water alarm. Settings can still be changed using the button. (see above, 
Configuration chapter) 

There is one each per pump of each of the following keys and LEDs. 

- HAND

Pressing this button will place the pump into 
manual operation. The green LED will blink. If 
the pump is being run via the manual function, 
then it will automatically shut off after 2 minutes. 

- 0

The pump is off. 
The green LED is off. 

- AUTO

The pump is switched based on level. 
The green LED stays on. 

CAUTION!

 

If power is interrupted during manual mode, then the control system will return to automatic 
mode. The operation modes "auto" and "0" remain stored, regardless of power interruptions. 

www.lesa.de

         

5

PS2 – SYSTEM ver.1.19

Summary of Contents for PS.2LCD

Page 1: ... 22179 Hamburg Germany Phone 49 40 641 00 41 Fax 49 40 641 18 36 PS 2LCD System com Micro controller Double pump controller Options Kompaktschaltschrank Micro Kompakt Kompaktschaltschrank mit Noteinspeisung und EVU Anschluß Operating Manual ...

Page 2: ...ions 3 Configuration control elements and function display 4 Configuration menu images and notes on configuring the parameters 5 Error reports in the display potential errors assistance 6 Test mode without pumps 7 Technical data 9 Norms 9 Annex Terminal block wiring diagrams Last update 05 01 2015 www lesa de 2 ...

Page 3: ...nal cover or working on the pumps the control system absolutely must be rendered current free via the pre fuse or a separate circuit breaker 1 4 Dangers of non compliance with safety information Non compliance with the safety information can lead to endangerment for persons and product system Non compliance with the safety information can lead to loss of all rights to damage compensation 1 6 Indep...

Page 4: ...ext display Thermal monitoring of the pumps Manual 0 Auto functions Pump switch off via turn off point and overrun Cancel button Runtime monitoring Forced pump switch on Variable staggered start delayed switch on Internal acoustic alarm Collective fault message zero potential High water alarm Memory no of pump starts Operating hours counter Input for high water float switch Pump change Forced swit...

Page 5: ...number of pump starts and motor current Moreover settings are made using the digital potentiometer If the knob is not moved for more than 20 seconds then the display will jump back to the default setting see above Configuration chapter Selection cancel Button Pressing this button will confirm the errors over current P1 P2 without load and will confirm thermal error 2 after remediating the cause Sh...

Page 6: ...e display s bottom line P1 Therm fault 1 Terminal 01 02 bi metal contact opened P1 Therm fault 2 Terminal 02 03 bi metal contact opened P2 Therm fault 1 Terminal 06 07 bi metal contact opened P2 Therm fault 2 Terminal 07 08 bi metal contact opened P1 or P2 Over current the respective motor circuit breaker has triggered Depending on how the PS2 SYSTEM s inputs are configured further error reports e...

Page 7: ...ssed Force activation Is deactivated 1 10s Is activated When the pumps are not triggered for 24 hours then they will automatically run for the configured Acoustic alarm Is deactivated is activated Is activated when there is an error the internal piezo buzzer will sound Intermitt alarm Is deactivated is activated Is activated The error report relay is clocked Instead of a blinking light a more econ...

Page 8: ...at time has passed there will be a change to the other pump This requires that both pumps be in automatic mode After three changes without interruption the alarm is additionally triggered and the display will show the runtime alarm report NEW Runtime monitoring The menu can be used to access the item running time max The default setting is for this value to be zero i e the function is deactivated ...

Page 9: ...nu under last error When the error is called up in the menu it can be deleted from memory using the cancel key Atex mode Atex mode has to be activated for pumps implemented in ex zones Atex mode impedes the pumps from being turned on via manual function via forced switch on or via remote control system until the switch off point is met If pumps are started via overrun time or manual function while...

Page 10: ...l probe The processor converts the input signal such that the correct level is displayed When the measurement range for the 4 20 mA probe is changed in the configuration menu the switch points will have to be re configured as they will have changed based on system reasons Thus the correct order will always be to first configure the probe s measurement range and then the switch points For use in an...

Page 11: ...hrough the additional use of thermistor relays and a corresponding pump lock For pumps over 7 5 KW it is generally recommended to use thermistor relays in order to secure the pumps are shut off even when the electronic system is out An external assessment module definitely needs to be used for assessing PTCs The inputs for the motor circuit breaker terminals 04 05 and 09 10 are configured such tha...

Page 12: ...ated then the pump will additional run for the duration of the overrun time configured The additional pressure sensor is always active irrespective of which system has been selected for level detection dynamic pressure bubbler system float switch or external 4 20 mA probe Float switch The inputs 11 12 to 17 18 can be configured for float switches The display shows which switch is connected Closing...

Page 13: ... is definitely established In order to avoid unnecessary interference peaks on the cable surplus cable should be rolled up In general it s always important to keep power electronics and the electronic system separate to the extent possible The bus cable should not come into contact with other cables prone to interference such as those coming from the circuit breaker or from volt and amp metres in ...

Page 14: ...ontrol cabinet section needed 136 5 x 136 5 mm Control device dimensions 290 x 125 x 60 mm Fuse control voltage 5 x 20 mm 100mA time lag Operating device lockable Attention The operating devices and or supplementary modules are not compatible with version 1 14 Technical specifications subject to modification Norms Applicable EC directives EC Low voltage directive 2006 95 EC EC Electromagnetic comp...

Page 15: ...www lesa de 15 PS2 SYSTEM ver 1 19 ...

Page 16: ...le Alarmmodule GSM Module Messumformer Fernwirk Pumpsysteme Messglocken Pneumatische Leitung Schaltanlagenbau Automatisierung Fernwirktechnik Freiluftsäulen komplett bestückt mit PS1 LCD PS2 LCD Kompaktschaltschrank LCD2 System Metall GfK Außenschränke Leersäulen EVU Anschlusssäule Verschraubungen für pneumatische Leitung Schwimmschalter Tauchsensoren Ultraschallsensoren Stabsonden Druckschalter A...

Reviews: