Level control
It can be selected whether the control system will run over the internal level sensor (dynamic pressure,
bubbler system), an external 4 - 20 mA level probe or float switch.
CAUTION!
The input for the high water alarm (terminal 23 / 24) is always active and can be implemented
as redundant monitoring. As soon as terminal 23 / 24 are connected, the high water alarm is triggered and the
pumps are switched with a delay.
When using external 4 - 20 mA level sensors and float switches installed in an explosive area, it will be
necessary to use components with the requisite approvals.
20 mA => Level
This setting adjusts the switch points and level display to a connected external
4 - 20 mA level probe. The processor converts the input signal such that the correct level is displayed.
When the measurement range for the 4 - 20 mA probe is changed in the configuration menu, the switch points
will have to be re-configured, as they will have changed based on system reasons. Thus, the correct order will
always be to first configure the probe's measurement range and then the switch points.
For use in an ex-zone, the corresponding requirements must be complied with, i.e. the 4 - 20 mA probe being
used must have the corresponding approval and a fitting ex-barrier. If the switch points are outside the level
probe's configured range, then the report will be shown
"Check switch points".
Country language
The default settings are German / English / French / Italian / Spanish / Dutch / Polish / Czech. The country
language can also be changed when service mode is deactivated.